BCE-95
Description
Building Control Element
Gamewell-FCI’s Building Control Element (BCE-95) is the
interface between the IF632 or IF650 Fire Alarm Control
Panel (FACP) and building functions that require a three
position (HOA) (On/Off/Auto) control capability. The BCE-
95 connects to the panel via the SLC circuit. The BCE-95
is assigned to a display (BCD) at the FACP via software
programming. The BCD provides annunciation, control and
feedback of the BCE-95 at the main FACP. The BCE-95
offers feedback input points for positive confirmation of the
controlled device’s activity.
The BCE-95 is for either surface or flush mounted and has
an integral LED that lights at device activation.
Operation
When an event is reported to the FACP that requires the
activation of the BCE-95, the FACP communicates via the
analog circuit to the BCE-95, and the selected building con-
trol relay is actuated. The integral LED then lights for
annunciation of the device.
In the event that a manual command is transmitted from
the building control display (BCD) at the control panel, the
BCE-95 device will respond and override the auto-pro-
grammed activation until the alarm event has been
resolved and reset
Programming
The BCE-95 is programmed by setting a single DIP switch
easily accessible on the device’s printed circuit board. The
DIP switch is used to set the address of the BCE-95. All
other programming is accomplished at the control panel,
either through a laptop computer or the control panel oper-
ator’s display.
Features
BCE-95
• Compatible with IF632 & IF650 FACPs.
• LED annunciates activation.
• Fully supervised.
• Surface or flush mounting.
• Field programmable.
• Style four, six, or seven wiring.
• Screw terminals for field wiring connections.
• Dry relay contacts.
• Provides controllable relay functions.
• Provides positive feedback of relay control.
• Separate on/start, off/stop operation.
An ISO 9000-2000 Company
SIGNALING
Microsoft® Windows® is a registered trademark of Microsoft® Corporation.
S521
FM
APPROVED 7300-1288:147
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
CS-2041 Rev. A page 1 of 2