English
Language : 

EDS11-169A Datasheet, PDF (3/8 Pages) Fuji Electric – PUM Series Multi-loop module type Temperature controller Analog input/output module[PUMV/N/T]
5. Display, configuration
5.1 Display
(1) Display:
Status display LED
(2 colors × 6 points)
(2) Display contents:
RUN/FAULT, RS-485 TX/RX, OUT/ERR by
loop (4 loops) (Functions are assigned to
LED of each channel)
5.2 Setting device
(1) Setting device: Rotary SW × 1
(2) Set contents: RS-485 Station No.
(Station No.= setting value + 1)
6. Power outage
(1) Impact of power outage:
Outage of 2ms or less ; no impact
(2) Operation after power outage:
Start from the first step (cold start)
(3) Memory backup:
Non volatile memory (EEPROM)
No. of update ; 100,000
7. Self diagnosis
Diagnosis method:
Program error monitoring by watch dog
timer
8. Structure
(1) Installation method:
DIN rail mounting or mounting with M3
screws inside a cabinet
(2) Dimensions: 30 (W) × 100 (H) × 85 (D) mm
(excluding terminal cover and projected
part)
(3) Weight:
Approx. 200 g
(4) Extrenal terminal
- Process value input/control output:
Detachable terminal block
(M3 screw × 20 terminals)
- Power supply connection:
Terminal block on the base part
(M3 screw × 2 terminals)
Power is supplied via side connectors
in case of lateral connecting. (Max. 33
units)
- RS-485 communication connection:
Terminal block on the base part
(M3 screw × 3 terminals)
RS-485 communication is connected via
side connectors in case of lateral con-
necting.
- Loader communication port:
2.5 diameter 3 prong mini-plug / jack
[on the front of the module]
(5) Case material: Polyphenylene oxide
(flame retardant grade : UL94V-0 equiva-
lent)
(6) Case color: Case ; red
Terminal, base part ; black
(7) Protection
- Body:
- Terminal:
IP20 grade protection
(ventilation slits on the top and the bot-
tom of the body)
IP00 grade protection, terminal cover is
available as an option
9. Normal operating condition
(1) Ambient temperature*: -10 to 50°C
* “Ambient temperature” is the tempera-
ture underneath the controller inside
the equpiment or the cabinet where
the controller is installed.
(2) Ambient humidity:
90% RH or less (non condensing)
(3) Vibration: 10 to 70Hz, 9.8m/s2 (1G) or less
(4) Warmup time:30 min. or more
10. Transporting, storage condition (packing con-
dition)
(1) Storage temperature: -20°C to 60°C
(2) Ambient humidity: 90%RH or less (no condensing)
(3) Vibration: 10 to 70Hz, 9.8m/s2 (1G) or less
(4) Shock:
294m/s2 (30G) or less
11. Packing list
-Temperature controller: 1unit
-Instruction manual: 1 copy
-250Ω resistance:
0, 2, or 4
(For no. points of voltage/current
input selected)
12. Loader software
(1) Distribution medium:
Free download from Fuji Electric Sys-
tems HP (http://www.fic-net.jp/eng/index.
html)
(2) Recommended operating environment
PC:
DOS/V (PC-AT compatible)
OS:
Windows XP (operating confirmed in
Japanese / English)
RAM: 256M bytes or more
Free space on the hardware: 500M bytes or more
Display resolution: 1024 × 768 dots or more
Serial interface: RS-232C 1 port
(without RS-232C, USB serial converter
cable required)
(3) Connection with PUM
Via loader interface on the front face of the module
(special cable available from Fuji is required) or via
RS-485