English
Language : 

EDS11-169A Datasheet, PDF (1/8 Pages) Fuji Electric – PUM Series Multi-loop module type Temperature controller Analog input/output module[PUMV/N/T]
PUM Series
Multi-loop module type
Temperature controller
DATA SHEET
Analog input/output module
[PUMV/N/T]
PUMV/N/T
PUMV/N/T is usable Analog I/O module as the accessory
I/O of PUM series. Each control module, 30mm wide, is
equipped the follows. PUMV is equipped 4 points of analog
input/output. PUMN is equipped 4points of analog input.
PUMT is equipped 4points of analog output. And all models
are equipped high-speed RS-485 port. By connecting with
PUM control modules, it realizes a compact and high-per-
formance system.
FEATURES
I. User-friendly structure and functions
1. Lateral connection with control module: Max.16 units
(64 channels) + event input/output module 16 units =
total 32 units
Simple wiring for power supply and communication
2. Detachable structure: Terminal block, main unit, and
the base part
→ Easy wiring with detachable terminal blcok
→ Main units exchangeable without re-wiring
3. Status LED for each input/output
→ Easy to detect input status and output status
4. Smart loader communication: Connect one module
and all connected modules are able to communicate
using a loader software.
II. Large scale system using high speed RS-485
1. Modbus RTU protocol for large volume communica-
tion
2. High-speed communication: Maximum 115.2kbps
3. Highly-efficient communication: Parameters dispersed
on the address map are re-allocated to contiguous
address
III. Various functions to enhance the control module func-
tions
1. Analog input
- Remote SV
2. Analog output
- Control output (included distribution output)
- Re-transmission output
SYSTEM SPECIFICATION
1. Product type: Multi-loop module type temperature
controller
2. Module type
1) Analog module: Total maximum 16 units
a) Control module (4 loop/unit)
b) Enhanced input/output (analog) module
- Analog input/output module
(Input/output 4 points/unit)
- Analog input module (Input 4 points/unit)
- Analog output module (output 4 points/unit)
2) Enhanced input/output (digital) module:
Maximum 16 units
- Event input/output module
(Input/output ; 8 points/unit)
3) Enhanced communication module: 1 unit
3. Connecting method:
Lateral connecting with connectors
- For power supply and RS-485 communication,
any one of connected modules is required to be
connected.
4. No. of loop, input/output
1) Control loop: Max. 64
2) No.of input / output: DI 128 points / DO 128 points
EDS11-169a
Date Apr. 1, 2011