English
Language : 

EDS11-105E Datasheet, PDF (3/6 Pages) Fuji Electric – FC SERIES SETTER (CONTINUOUS OUTPUT TYPE)
(3) Communication interface
(a) T-link: Private interface
Transmission speed: 500Kbps
No. of units connectable: 32 max.
Transmission distance: 1km max.
Transmission form: Multi-drop
Control method: I/O transmission and message
(b) RS-422A/485: Universal interface
Transmission speed: 2400, 4800, 9600 or 19200bps
configurable
No. of units connectable: 31 max.
Transmission distance: 1km max.
Transmission form: Multi-drop
Control method: Polling/selecting
(c) CC data line: Private interface
Transmission speed: 19.2Kbps
No. of units connectable: 15 max.
Transmission distance: 500m max.
Transmission form: Multi-drop
Control method: Polling/selecting
7. Other functions
Data protective function by pass code
8. Operating conditions
Power supply: Select from 3 types
24V DC (20 to 30V DC)
100V AC (85 to 132V/47 to 63Hz AC)
200V AC (187 to 264V/47 to 63Hz AC)
Power consumption:
Approx. 11W (DC)
Approx. 20VA (AC)
Dielectric strength:
1500V AC, 1 min.
Insulation resistance:
500V DC, 100MΩ or more
Ambient temperature:
0 to 50°C
Ambient humidity:
90% RH or less
Enclosure:
Steel case
Rating plate (Name plate):
100 (H) x 70 (W) mm, white acryl
Dimensions: 144 (H) x 72 (W) x 391 (D) mm, IEC
(DIN) standard
Mass (weight): Approx. 2.9kg
Mounting method:
Flush indoor mounting; vertical mounting.
Mountable on tilted surface angle "α"
CODE SYMBOLS
1 2 3 4 5 6 7 8 9 10
PNF 1
5 -0
A
B
A
B
1
2
3
Y
T
R
S
C
Description
Process value input signal
1 to 5V DC
4 to 20mA DC
Setting method
L type
R-L type
Power supply
24V DC (20 to 30V DC)
100V AC (85 to 132V/47 to 63Hz AC)
200V AC (187 to 264V/47 to 63Hz AC)
Transmission functions
None
T-link
RS-422A
RS-485
CC data line
α=0°to 90°
Finish color: Munsell N 1.5 for both front panel and
case
Scope of delivery: Setter and mounting bracket
3