2nd layer setting procedures
PULS
Pulse no. per revolution setting
dIA
Roller diameter value setting
CtHy
Control Hysteresis value setting
ALHy
Alarm Hysteresis value setting
Pulse no. per revolution setting
1. Press the "Set” button continuously for at least two seconds, the display will show
"PULS", now the meter is ready for the "Pulse no. per revolution" setting.
2. Use the "▼” button and the "▲” button to adjust the desired "Pulse no. per
revolution".
Note: When adjusting the value, the "SV” indicator will light.
Roller diameter value setting
1. After setting the "Pulse no. per revolution", press the " Set” button twice, the display
will show dIA ", now the meter is ready for the "Roller diameter value" setting.
2. Use the "▼” button and the "▲” button to adjust the "Roller diameter value" in the
unit of cm.
Note: When adjusting the value, the "SV” indicator will light.
Control Hysteresis value setting
1. After setting the "Roller diameter value", press the "Set” button twice, the display
will show “CtHy", now the meter is ready for the "Control Hysteresis value" setting.
2. Use the "▼” button and the "▲” button to adjust the desired Hysteresis value".
Note: When adjusting the value, the "SV” indicator will light.
Example: Control value : 500, Control Hysteresis value : 5
The state of the control relay will stay On for measured values up to 500. The control
relay will turn Off when the measured value goes down to 495.