U2100B-MFP Datasheet, PDF (4/13 Pages) List of Unclassifed Manufacturers – Timer Control for Triac and Relay
Figure 4. Three-wire Circuit
L
Control
N
For three-wire switch systems, two operational modes are possible:
– Zero voltage switch operation for triac control
– Static operation for relay control
Mode Selection Pin 4 and The operational modes can be selected by the external voltage at the synchronous input
Supply Voltage Pin 2
pin 4 (clamping). The mode selection determines the current requirement of the relay's
or triac's driver stage and hence the selection of the supply voltage.
Zero Voltage Switch
Operation (Figure 5)
Selection condition:
V4 = internal synchronous limitation, without external clamping
R1 ≈
0.85
-V----M-----–-----V----S-
2 Itot
Itot = IS + Ip + IX
where:
IS = Supply current of the IC without load
IP = Average trigger current IG
IX = External circuit current requirement
VM = Mains voltage
Required firing pulse width tp
tp
=
2-ω- arcsin
⎛
⎝
-IP-L-----××-----V-----2M--⎠⎞
where:
IL = Triac latching current
P = Power at load Z
Rsync[kΩ] ≈
-V----M----[--V----]---×----------2----s---i-n-----(---ω----×------t--p---[-s---]---)---–-----0---.--7- – 176
1.8 × 10-2
4 U2100B
4769B–INDCO–12/04