English
Language : 

QC01 Datasheet, PDF (3/3 Pages) List of Unclassifed Manufacturers – Smart - Control Modules
Product data sheet
Sheet No.: 1.604.01 - Rev: E - Page 3 of 3
Date:
October, 2006
FieldQ
Wiring & Electrical Specifications QC01 & QC 02
QC01
1-2 Feedback 2
3-4 Feedback 1
5-6 Control supply
voltage
7-8 Power supply
voltage
Field wiring Unit wiring
0-30 VDC/VAC
1
0.5 Amax. 15VAmax.
2
0-30 VDC/VAC
3
0.5 Amax. 15VAmax.
4
5
24 VDC +/- 15%
6
-7
24 VDC +/- 15%
+8
QC01, 24VDC electric connections, separate circuits
1-2 Feedback 2,
3-4 Feedback 1
5-6 Control
7-8 Power supply
voltage
Field wiring Unit wiring
0.5 Amax. 15VAmax.
1
2
0.5 Amax. 15VAmax.
3
4
5
6
-7
24 VDC +/- 15%
+8
QC01, 24VDC electric connections, common “-”
Electrical data QC01 : 24VDC
Power supply input :
Voltage
24 VDC (±15%)
Maximum current
125 mA
Power (nominal)
2.5 W
Control signal input :
Voltage
24 VDC (±15%)
Maximum current
5 mA
Contacts
Potential free
Feedback switches output:
Voltage
0-30 VDC
Current DC
500 mA (maximum)
1 mA (advised minimum)
Resistance (nom.) 0.5 Ohm (On state)
Maximum power
15 W
Electric contacts
Potential free
Polarity:
Dependent
Power supply
Independent
Control signal + feedback switches.
- For Non-Incendive (Cl. I Div2) or Non-Sparking (Zone 2) hazardous
area applications, see Installation Guide : DOC.IG.QC01.1
QC02
Field wiring Unit wiring
1-2 Power supply
voltage
3-4 Control supply
voltage
5-6 Feedback 1
7-8 Feedback 2
85-254 VAC
85-254 VAC
0-254VAC/VDC
150mAmax. 15VAmax.
0-254VAC/VDC
150mAmax. 15VAmax.
1N
2L
3
4
5
6
7
8
QC02, 85-254VAC electric connections, separate circuits
Field wiring Unit wiring
1-2 Power supply
voltage
3-4 Control supply
voltage
5-6 Feedback 1
7-8 Feedback 2
85-254 VAC
150mAmax. 15VAmax.
150mAmax. 15VAmax.
1N
2L
3
4
5
6
7
8
QC02, 85-254VAC electric connections, single power
Electrical data QC02 - 85-254VAC
Power supply input :
Voltage
85-254V (rated mains 95-230V) 50/60Hz
Maximum current (* 60 mA
Power (nominal)
2.8 W
Control signal input :
Voltage
85-254V 50/60Hz
Maximum current
2.5mA at 115 VAC
5mA at 230 VAC
Feedback output:
Voltage
0-254 Vac/dc 50/60Hz
Maximum current
150mA
(AC or DC)
Maximum power
15 W
Electric contacts
Potential free
(* The QC02 module has a fuse in the supply live line. It is not
allowed to replace this fuse in the field.
- For Non-Incendive (Cl. I Div2) or Non-Sparking (Zone 2) hazardous
area applications, see Installation Guide : DOC.IG.QC02.1
TM
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can
be obtained from our web site www.Fieldq.com or from your nearest Valve Automation Center: America's: +1 813 630 2255
(fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 626 24 515 (fax +65 626 80 028)