English
Language : 

CONTROL-PIONT-MODULE5000 Datasheet, PDF (3/3 Pages) List of Unclassifed Manufacturers – Control Point Module (CPM) 5000
®
Transceiver Bit Rate
78kbps.
Maximum Nodes Per Channel
64 (-40 to +85°C).
Network Length in
Free Topology only
1000m (3280 feet) \maximum total wire
with one repeater.\500m (1640 feet)
maximum total wire with no repeaters.
Network Bus Polarity
Insensitive.
Power-down Network Protection
High impedance when unpowered.
Supply Voltage
3.0V to 3.6V.
Double row 0.1” center connector
for I/O, power, and communications.
Network Termination
One terminator in free topology.
Two terminators in bus topology.
Operating Temperature
-40°C to +85°C.
Non-operating Temperature
-40 to +85°C.
Operating Humidity
25 to 90% RH @ 50°C, non-condensing.
Non-operating Humidity
95% RH @ 50°C,
non-condensing.
Dimensions
1.7”W x 1.175”H x 0.63”D.
Parameter
ESD
Radiated EM
susceptibility
Fast
Transient
Burst
Immunity
Surge
Immunity
Common
Mode Noise
Immunity
Radiated EMI
Agency
Spec or
Standard
IEC1000-4-2
IEC1000-4-3
IEC1000-4-4
IEC1000-4-5
IEC1000-4-6
EN55022
FCC Part 15
Level
4 (20 MHz
and greater)
4 (20 MHz
and greater)
3 (10 MHz)
3 (10 MHz)
3
4
3
B
B
High Voltage HIPOT
60s
Isolation (0.5 mA max
0–60 Hz
leakage)
Contin.
Shock
Vibration
Method Limit Unit
Air Discharge 15 kV
Contact Discharge 8 kV
Air Discharge 8 kV
Contact Discharge 6 kV
10 V/m
Network
Cable Clamp
2
kV
2 kV
BCI clamp on
Network Cable
10
Vrms
Disconnect MOV 2.4 kVrms
3 ms half-sine
8 Hz – 2 kHz
277 Vrms
100
(peak)
g
1.5
peak- g
to-peak
variations in node distribution, node temperature, node voltage, wire characteristics, and
FT 5000 Smart Transceiver characteristics, and allow for an average wire temperature of
up to +55°C.
2. Safety agency hazardous voltage barrier requirements are not supported.
3. The I/O pins of P1 connect directly to the FT 5000 Chip and do not contain additional
protection beyond what is available with a typical advanced CMOS device.
4. For ESD protection at 5 MHz and 10 MHz operations, your design should include ferrite
beads in series with the network pins. An example part that meets the requirements is a
Fair-Rite Products Corp 2743007112 bead on lead. Beads are not required for operations
at 20 MHz or higher.
5. For wire specifications, see Junction Box and Wiring Guidelines for Twisted Pair
LonWorks Networks, 005-0023-01 Rev D or later.
6. FT 5000 Smart Transceivers and Control Modules were not designed for use in
equipment or systems which involve danger to human health or safety or a risk of
property damage, and Echelon assumes no responsibility or liability for use of the FT
5000 Smart Transceivers or Control Modules in such applications.
ORDERING INFORMATION
CPM 5000
55040R-10
(RoHS-compliant)
LonWorks Twisted Pair Control Module User’s Guide 078-0015-01
(to be ordered separately – not shipped with product)
Notes
1. Maximum distance figures are based©o20n14 Echelon, LonWorks, and the Echelon logo are trademarks of Echelon Corporation registered in the United States and other
countries.IzoT is a trademark of Echelon Corporation. Content subject to change without notice.
www.echelon.com