SNAP-TEX-CBO6 Datasheet, PDF (22/29 Pages) List of Unclassifed Manufacturers – SNAP TEX Cables and Breakout Boards
SNAP TEX Cables and Breakout Boards
SNAP-IDC-HDB and SNAP-ODC-HDB Breakout Boards
SNAP-IDC-HDB, SNAP-IDC-HDB-FM, SNAP-ODC-HDB, and
SNAP-ODC-HDB-FM breakout boards provide LED indicators
and easily accessible fused connectors for points on 32-
channel digital input or output modules.
See Opto 22 form 1547, the High-Density Module User’s Guide,
for SNAP-IDC-HDB and SNAP-ODC-HDB breakout rack wiring
and jumper settings.
Specifications
SNAP-IDC-HDB and SNAP-IDC-HDB-FM Breakout Racks for High-Density Digital Input Modules
Used with SNAP-IDC-32, SNAP-IDC-32-FM, SNAP-IDC-32N, and SNAP-IDC-32DN
Connectors
40-pin header connects to 32-channel input module using SNAP-HD-BF6 header cable.
32 signal input connectors; each signal connector has a corresponding common connector.
For each zone of 8 signal inputs, 1 connection for either module common or field common.
Indicators
1 LED for each signal input (32 signal LEDs total)
1 power status LED for each zone of 8 signal inputs (4 power LEDs total)
Fusing
1 A fuses; 2 fuses for each zone of 8 signal inputs (8 fuses total)
Replace with Pudenz 1 A automobile mini-fuse or equivalent.
Jumpers
For each zone of 8 signal inputs, 1 jumper controls whether module common or field common
is used.
Voltage
32 VDC maximum, 12-24 VDC nominal
Agency
Approvals
SNAP-IDC-HDB: UL, CE, RoHS, DFARS
SNAP-IDC-HDB-FM: FM, CE, RoHS, DFARS
Warranty
30 months from date of manufacture
SNAP-ODC-HDB and SNAP-ODC-HDB-FM Breakout Racks for High-Density Digital Output Modules
Used with
SNAP-ODC-32-SRC, SNAP-ODC-32-SRC-FM,
SNAP-ODC-32-SNK, and SNAP-ODC-32-SNK-FM
Connectors
40-pin header; connects to 32-channel sourcing or sinking module using
SNAP-HD-BF6 header cable.
32 signal output connectors; each signal connector has a corresponding common connector.
For each zone of 8 signal outputs, 1 connection for either module common or field common.
Indicators
1 LED for each signal output (32 signal LEDs total)
1 power status LED for each zone of 8 signal outputs (4 power LEDs total)
Fusing
1 A fuses; 1 fuse for each signal output (32 signal fuses total)
Replace with Pudenz 1 A automobile mini-fuse or equivalent.
Jumpers
For each zone of 8 signal inputs, 1 jumper controls whether module common or field common
is used.
Voltage
32 VDC maximum, 12-24 VDC nominal
Agency
Approvals
SNAP-ODC-HDB: UL, CE, RoHS, DFARS
SNAP-ODC-HDB-FM: FM, CE, RoHS, DFARS
Warranty
30 months from date of manufacture
PAGE
22
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com
SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com
© 2008–2012 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.