PDUMH20AT Datasheet, PDF (2/4 Pages) List of Unclassifed Manufacturers – Single-Phase Auto Transfer Switch / Metered PDU, 1.9kW 20A 120V, 1U Horizontal Rackmount, 16 5-15/20R outlets
is connected to a separate UPS system (in a two-UPS environment, the primary input cable must be supported by an online UPS with zero transfer time
similar to Tripp Lite SmartOnline series)
Advanced ATS configurations utilizing separate mains circuits, backup generators and even separate out of phase utility power grid feeds are fully
supported
On-board ATS processor constantly evaluates power quality on both inputs to prevent transfer to the secondary source when unavailable or of lower
quality than the primary source
Super-fast switchover between primary and secondary power sources occurs in 2-7 milliseconds
Built-in card slot supports optional SNMPWEBCARD for permanent upgrade to a switched & monitored PDU system
Outlets are factory programmed for sequential turn-on at 250 milliscond intervals when the PDU is first energized to prevent inrush-related equipment
interaction on startup
Front panel LEDs confirm power availability on both input lines
TAA Compliant Version Available - Order Tripp Lite PDUMH20ATAA
Specifications
OVERVIEW
PDU Type
Auto-Transfer Switch; Metered
OUTPUT
Output Capacity Details
Frequency compatibility
Output VA
Output nominal voltage
Outlet quantity / type
Outlet Type
1.9kW (120V input), 2.0kW (127V input), 1.6kW (100V input); 20A maximum (Agency de-rated to 16A continuous)
60 Hz
2400
100-127V nominal, single phase
16 NEMA 5-15/20R
NEMA 5-15R, NEMA 5-20R
INPUT
PDU Input Voltage
Maximum Input Amps (A)
Maximum Input Amps (A) Details
PDU Plug Type
Input cord length details
Phase
100; 120; 127
20
Agency de-rated to 16A maximum
NEMA 5-20P; NEMA L5-20P
Both input cables are 12 ft / 3.6m - the cables each terminate to a L5-20P locking plug on the input side. Two
included 6 inch plug adapters convert the locking plugs to NEMA 5-20P plugs
Single-Phase
LEDS ALARMS & SWITCHES
Front panel LEDs
16 front panel LEDs display power on - off status for each outlet, plus 2 LEDs for power status on each input line
cord. Digital Current Meter Display shows total load consumption of connected equipment in amps
PHYSICAL