English
Language : 

PDUMH15ATNET Datasheet, PDF (2/5 Pages) List of Unclassifed Manufacturers – Single-Phase Auto Transfer Switch / Switched PDU, 1.4kW 15A 120V, 1U Horizontal Rackmount
ATS configurations enable hot-swappable UPS protection when used with a single UPS and redundant UPS protection when each input is connected to a
separate UPS system (in a two-UPS environment, the primary input cable must be supported by an online UPS similar to Tripp Lite SmartOnline)
Advanced ATS configurations using separate mains circuits, backup generators and out of phase utility feeds are fully supported
On-board processor evaluates power quality on both inputs to prevent transfer to the secondary source when unavailable or of lower quality than the
primary source
2-7 millisecond transfer time between primary and secondary inputs
DHCP/Manual configuration support; Supports HTTP, HTTPS, PowerAlert Network Management System, SMTP, SNMPv1, SNMPv2, Telnet, SSH, FTP,
DHCP, BOOTP, NTP protocols
Compatible with optional ENVIROSENSE temperature monitor
Outlets are factory programmed for sequential turn-on at 250 millisecond intervals as the PDU is first energized
Front panel LEDs confirm power availability on primary / secondary inputs and each output receptacle
TAA Compliant Version Available - Order Tripp Lite PDUMH15ATNETAA
Specifications
OVERVIEW
PDU Type
Auto-Transfer Switch; Switched
OUTPUT
Output Capacity Details
Frequency compatibility
Output nominal voltage
Outlet quantity / type
Outlet Type
Customized load management
receptacles
1.4kW (120V input), 1.5kW (127V input), 1.2kW (100V input); 15A maximum (Agency de-rated to 12A continuous)
60 Hz
100-127V nominal, single phase
8 NEMA 5-15R
NEMA 5-15R
8 individually controlled outlets
INPUT
PDU Input Voltage
Maximum Input Amps (A)
Maximum Input Amps (A) Details
PDU Plug Type
Input cord length (ft.)
Input cord length (m)
Phase
100; 120; 127
15
Agency de-rated to 12A continuous
NEMA 5-15P
12
3.66
Single-Phase
LEDS ALARMS & SWITCHES
Front panel LEDs
10 front panel LEDs display power on - off status for each outlet, plus 2 LEDs for power status on each input line
cord. Digital Current Meter display shows total output power consumption in amps.