English
Language : 

PDUBHV20 Datasheet, PDF (2/4 Pages) List of Unclassifed Manufacturers – Single-Phase Hot-Swap PDU, 3.2-3.8kW 16A 200-240V, 2U Horizontal Rackmount, 6 C13 and 2 C19 outlets, set of 2 C20 inputs
is removed and replaced with a fresh one
Once the new UPS is up and running with all connection s restored, set the switch back to the UPS setting to once again provide fully-conditioned UPS
power to connected equipment
TAA Compliant Version Available - Order Tripp Lite PDUBHV20TAA
Specifications
OVERVIEW
PDU Type
OUTPUT
Output Watt Capacity (watts)
Output Capacity Details
Frequency compatibility
Output nominal voltage
Outlet quantity / type
Outlet Type
INPUT
PDU Input Voltage
Maximum Input Amps (A)
Input connection type
PDU Plug Type
Input cord length (ft.)
Input cord length (m)
Phase
LEDS ALARMS & SWITCHES
Switches
Front panel LEDs
PHYSICAL
Shipping Dimensions (HWD/in)
Shipping Dimensions (HWD/cm)
Shipping weight (lbs)
Hot-Swap
3680
3.3kW (208V input), 3.5kW (220V input), 3.7kW (230V input), 3.8kW (240V input), 3.2kW (200V input); 20A
maximum (Agency de-rated to 16A continuous)
50 / 60 Hz
200-240V nominal, single phase
6 C13 and 2 C19 outlets support critical connected loads; 1 designated pass-through C19 outlet supports C20 input
plug from UPS
C13, C19
200; 208; 220; 230; 240
16
UTILITY & UPS inputs are available from separately labelled C20 inlets, compatible with included C19-C20
interconnect cables or with compatible user-supplied cabling
IEC-320 C20
6
1.83
Single-Phase
Manual 2 position transfer switch offers fast switching between UPS and Utility operating modes in less than 6
milliseconds
Lighted indicators confirm UPS and Utility switch position and operating mode
9.84 x 22.75 x 9.44
25 x 57.8 x 24
11
2/3