PDUBHV20 Datasheet, PDF (1/4 Pages) List of Unclassifed Manufacturers – Single-Phase Hot-Swap PDU, 3.2-3.8kW 16A 200-240V, 2U Horizontal Rackmount, 6 C13 and 2 C19 outlets, set of 2 C20 inputs
Single-Phase Hot-Swap PDU, 3.2-3.8kW 16A
200-240V, 2U Horizontal Rackmount, 6 C13 and 2
C19 outlets, set of 2 C20 inputs
MODEL NUMBER: PDUBHV20
Highlights
Single phase 16A 200-240V
Hot-swap PDU
Enables live replacement of a
standard UPS with zero downtime
2U horizontal rackmount
installation
Compatible with any 200-240V
UPS with a C20 input
Manual transfer switch controls
PDU input power source
Pair of C20 compatible inputs
connect to separate Utility and
UPS inputs
8 built in outlets (6 C13 / 2 C19)
Applications
Hot-swap PDUs are ideal to install
along with standard UPS systems to
Description
ensure that connected networking
Tripp Lite’s Hot-swap PDU systems enable live-replacement of standard UPS systems for maintenance with no
interruption of connected server or networking loads. Dual input power cables support PDU connection to
separate Utility and UPS power sources. Manual transfer switch with lighted status indicators controls the source
equipment will see no power
interruption as the UPS is serviced,
replaced or upgraded
of power to connected equipment between Utility and UPS. Set the switch to UPS during normal operation and
connected equipment will receive full-time conditioned power from the UPS. Set the switch to Utility to
momentarily power connected equipment from the Utility line cord and bypass the UPS while the UPS system is
removed and replaced with a fresh one. Once the new UPS is up and running with all data and electrical
connections restored, set the switch back to the UPS setting to once again provide fully-conditioned UPS power
to connected equipment.
Package Includes
Hot-swap PDU System
2U mounting brackets
Set of 2 C19-C20 interconnect
cables
User manual with warranty
Features
information
Tripp Lite Hot-swap PDU systems support live-replacement of standard UPS systems for maintenance with
no interruption of connected server or networking loads
PDUBHV20 is universally compatible with any Tripp Lite or other brand of 200-240V UPS rated 2000 to 3000VA with a C20 input cable
2U horizontal rackmount form factor compatible with 2 or 4 post racks
Supports space saving rear-post mounting in the same rack space as many Tripp Lite Rackmount UPS systems (select installations, see manual)
Pair of detachable PDU input cables connect to separate Utility and UPS power sources (2 5ft. C19-C20 and 2 6ft. C13-C14 interconnect cables included
- user supplied alternate cabling supported)
6 C13 and 2 C19 outlets support critical networking loads in both Utility and UPS operating modes
One additional C19 pass-through outlet supports UPS input power cord
Dual input power cables support PDU connection to separate Utility and UPS power sources
Manual transfer switch with lighted status indicators controls the source of power to connected equipment between Utility and UPS
Set the switch to UPS during normal operation and connected equipment will receive full-time conditioned power from the UPS
Set the switch to Utility to bypass the UPS and provide connected equipment with unfiltered power directly from the Utility line cord while the UPS system
1/3