English
Language : 

G3PA Datasheet, PDF (7/16 Pages) List of Unclassifed Manufacturers – Power Solid-state Relay
3. Insert the cartridge into the opening of the G3PA so that side A
and side B are even.
Side A
Side B
4. Tighten the screws on both the corners with a tightening torque of
0.59 to 0.78 N·m.
5. Tighten the screws on both the sides with a tightening torque of
0.59 to 0.78 N·m.
6. Attach the terminal cover.
7. Switch on the power and check the G3PA to be sure it works
properly.
I Linking Terminal Connection
• Connecting with linking terminal for G3PA-210B(L)-VD, -220B(L)-
VD, -240B(L)-VD and G3PA-420B-VD(-2), G3PA-430B-VD(-2).
SSR1
SSR2
SSR1
SSR2
• Connecting with linking terminal for G32A.
SSR G32A Unit
SSR
G32A Unit
1. When SSRs are close
mounted, loosen the
M3.5 Sems screw and
flip the linking terminal
down.
2. Insert the linking
terminal securely
into the center of
the screw and
tighten the screw.
1. When SSR are close
mounted, loosen the
M3.5 Sems screw on
the G32A and flip the
linking terminal down.
*
* The cover will not fit if
the terminal protrudes.
2. Insert the linking termi-
nal securely into the
center of the screw and
tighten the screw. En-
sure that the linking ter-
minal does not pro-
trude.
Connect the terminal with power off.
Linking terminal
Refer to the instruction manual for
the G32A-A Power Device Cartridge
to replace the G3PA's triac part.
Linking terminal
G3PA-420B-VD
Linking
terminal
Linking
terminal
When the temperature indicator has turned from pink to red, the G32-A-A Power Device Car- Use the terminal cover to prevent accidents
tridge may have malfunctioned, in which case the cartridge must be replaced with a new one. due to electric shock.
Power Solid-state Relay G3PA-(VD)