English
Language : 

FAA01DM24 Datasheet, PDF (2/3 Pages) List of Unclassifed Manufacturers – Timers Delay on Operate
FAA01, FAA08
General Specifications
Function and Time Setting
Indication for
Power supply On
Output ON
Environment
Degree of protection
Operating temperature
Ambient humidity
Housing dimesions
Weight
CE marking
EMC
Immunity
Emission
LED, green
(flashing when timing)
LED, red
IP 40 (front panel)
-10 to +55 °C (14 to 131 °F)
35 to 85% RH
48 x 48 mm
Approx. 95 g
Yes
Electromagnetic Compatibillity
According to EN 61000-6-1
According to EN 61000-6-3
Upper right knob:
Setting of function
A - delay on operate
B2 - simmetrical recycler
E - interval
J - one shot
Lower right knob:
Time unit selector
sec (seconds)
min (minuts)
hrs (hours)
10h (10 hours)
Lower left knob:
Time range selector
1.2, 3, 12 and 30
Centre knob:
Time setting on relative
scale
Mode of Operation
Function A
Delay on operate
The set delay period begins
as soon as the power supply
is connected. At the end of
the set delay the relay oper-
ates and doesn’t release
until the power supply is
interrupted for at least 100
ms.
Function B2
Symmetrical recycler
(ON first)
The relay operates and the
time period start as soon as
the power is applied. At the
end of the first set time peri-
od, the relay releases. At the
end of the second time peri-
od (equal to the first), the
relay operates again. This
sequence continues with
equal ON- and OFF- time
periods until the power sup-
ply is interrupted for at least
100 ms.
Function E
Interval
The relay operates and the
time period begins as soon
as the power is applied. The
relay releases at the end of
the time period or when the
power supply is disconnect-
ed for at least 100 ms.
Function J
One shot
The time period begins as
soon as the power supply is
connected and at the end of
this period the relay operates
for 1s.
Range and operation mode selection
Power indicator (green)
(Flashes when timer operates;
on when timer stops operating)
Output indicator (red)
(Lit when output is ON)
Operating mode display window
Operating mode selector
(function A, B2, E, J)
Time range selector
(1.2, 3, 12 and 30 at full scale)
Scale range display windows
Time unit display window
Time unit selector (sec, min, hrs, 10h)
Time setting knob (set time)
2
Specifications are subject to change without notice (26.07.05)