English
Language : 

8340-T Datasheet, PDF (5/6 Pages) ETAL Group – Power supplies, control equipment, communication systems, EDP systems
Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-T...
Accessories
Connector bus links -K10
X210 589 01/2.5 mm2, (AWG 14) (black) up to 20 A max. load
X210 589 02/1.5 mm2, (AWG 16) (brown) up to 13 A max. load
50 pin lugs to
DIN 46230
tinned copper
ø2.5
.099
Busbar 1-pole
Y 308 495 01
The one metre long busbars can be cut to suitable lengths.
Plug-on caps can be fitted on the ends to provide brush
contact protection.
Imax - busbar 100 A (40 °C)
995+2
39.173+.079
marking 4 x on busbar
Elektrotechnische Apparate Gmb
D-90418 Altdorf bei Nürnberg
Art.-Nr. Y 308 495 01
IEC 664 500 V/100 A (40 °C)
Elektrotechnische Apparate GmbH
D-90418 Altdorf bei Nürnberg
Art.-Nr. Y 308 495 01
IEC 664 500 V/100 A (40 °C)
4±0.2
.157±.008
19
.748
4.6
.181
51 x 19 = 969
51 x .748 = 38.150
Plug-on cap, 1-pole
Y 307 851 01
1.5
.059
Busbar 2-pole
Y 308 496 01
Imax - busbar 100 A (40 °C)
995+2
39.173+.079
marking 4 x on busbar
Elektrotechnische Apparate GmbH
D-90418 Altdorf bei Nürnberg
L1
L2
L1
Art.-Nr. Y 308 496 01
IEC 664 500 V/100 A (40 °C)
L2
L1
L2
L1
L2
L2
L1
Elektrotechnische Apparate Gmb
D-90418 Altdorf bei Nürnberg
L1
L2
L1
Art.-Nr. Y 308 496 01
IEC 664 500 V/100 A (40 °C)
L2
L1
L2
L1
L2
4±0.2
.157±.008
19
.748
15.8
.622
51x19=969
51 x .748 = 38.150
Plug-on cap, busbar 2/3-pole
Y 308 506 01
1.5
.059
Busbar 3-pole
Y 308 497 01
Imax - busbar 100 A (40 °C)
995+2
39.173+.079
marking 4 x on busbar
Elektrotechnische Apparate GmbH
D-90418 Altdorf bei Nürnberg
L1
L2
L3
Art.-Nr. Y 308 497 01
IEC 664 500 V/100 A (40 °C)
L1
L2
L3
L1
L2
L2
L3
Elektrotechnische Apparate GmbH
D-90418 Altdorf bei Nürnberg
L2
L3
L1
Art.-Nr. Y 308 497 01
IEC 664 500 V/100 A (40 °C)
L2
L3
L2
L2
L3
4±0,2
.157±.008
19
.748
15.8
.622
50 x 19 = 950
50 x .748 = 37.402
Plug-on cap, busbar 2/3-pole
Y 308 506 01
1.5
.059
1
Supply terminal Imax 63 A
Y 308 504 01
Max. tightening torque of terminal screw 2 Nm
Max. cable cross section: 25 mm2 / single strand
16 mm2 / multistrand
4
with wire end ferrule
1.5
.157
.059
A
13
18.4
.512
.724
Caution:
When using multipole busbars please leave at least one pole’s
width between two adjacent line entry terminals.
1646
This
is
a
metric
design
and
millimeter
dimensions
take
precedence
(
mm
inch
)
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved.Product markings may not be exactly as the ordering codes.
Errors and omissions excepted.
www.e-t-a.de