English
Language : 

8340-T Datasheet, PDF (1/6 Pages) ETAL Group – Power supplies, control equipment, communication systems, EDP systems
Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-T...
Description
Single, two and three pole magnetic and hydraulic-magnetic circuit
breakers with trip-free mechanism and toggle actuation. A choice of
fast magnetic only or hydraulically delayed switching characteristics
(S-type MO or HM CBE to EN 60934) ensures suitability for a wide
range of applications. Featuring a combi-foot design for symmetric rail
mounting. Low temperature sensitivity at rated load.
Approved to CBE standard EN 60934 (IEC 60934).
Typical applications
Power supplies, control equipment, communication systems, EDP
1
systems.
8340-T...
single pole
three pole
Standard current ratings and typical internal resistance values
Current
rating (A)
0,02
0,05
0,1
0,25
0,5
0,75
1
2
2,5
3
5
6
8
10
12
15
16
20
25
30
40
50
Internal resistance values (Ω) per pole
F1
F2
K1, M1, T1 K2, M2, T2
1 493
953
2 669
2 457
276
152
452
376
58
37
100
94
8,2
6,0
15,5
14,7
2,3
1,47
3,9
3,2
0,98
0,63
1,65
1,56
0,58
0,35
0,95
0,90
0,145
0,096
0,26
0,20
0,096
0,061
0,15
0,15
0,065
0,048
0,10
0,10
0,025
< 0,02
0,042
0,040
< 0,02
< 0,02
0,029
0,028
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,01
-
< 0,01
-
< 0,01
-
< 0,01
-
Technical data
For further details please see chapter: Technical Information
Voltage rating
3 AC 415V; AC 240V (50/60Hz); DC 80V
(higher DC voltages to special order)
Current rating range
0.02...50 A DC
0.02...30 A AC
Auxiliary circuit
1 A, AC 240 V/DC 65 V; 0.5 A DC 80 V
Typical life 3 AC 415 V AC 240 V:
0.02...30 A 6,000 operations at 1 x IN, inductive
10,000 operations at 1 x IN, resistive
WDC 80 V: 0.02...25 A 6,000 operations at 1 x IN, inductive
0.02...30 A 10,000 operations at 1 x IN, resistive
40 + 50 A 6,000 operations at 1 x IN, resistive
Ambient temperature
-40...+85 °C (-40...+185 °F)
Insulation co-ordination
(IEC 60664 and 60664A)
rated impulse
pollution
withstand voltage degree
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A)
operating area
test voltage AC 3,000 V
Line to Load
test voltage AC 1,500 V
pole to pole (2- and 3-pole) test voltage AC 1,500 V
main to auxiliary circuit test voltage AC 1,500 V
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity
6 x IN at AC;
IEC 60934 - test sequence E 4 x IN at DC
Interrupting capacity IN
(UL 1077)
AC: 1-pole
2-pole
3-pole
DC: 1-pole
2-pole
0.02...20 A
25...30 A
AC 250 V/3,500A AC 250 V/3,500A
AC 250 V/3,500A AC 250 V/5,000A
3AC 250V/3,500A 3AC250V/5,000A
0.02...50 A
DC 80 V/3,500 A
0.02...30 A
DC 80 V/3500 A
Degree of protection
(IEC 60529/DIN 40050)
operating area IP40
terminal area IP20
Vibration
with toggle down:
directions 1, 2, 3, 4, 5:
with curves F1, F2:
10 g at 0.9 IN
10 g at 1 x IN
10 g at 0.8 x IN in all planes.
(57-2000 Hz) ± 0.76 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
directions 1, 2, 3, 4, 5:
direction 6:
with curves F1, F2:
100 g (11 ms) at 1 x IN
100 g (11 ms) at 0.8 x IN
100 g (11 ms) at 0.8 x IN
to IEC 60068-2-27, test Ea
Corrosion
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity
240 hours at 95 % RH,
to IEC 60068-2-78, test Cab
Mass
approx. 98 g per pole
1646
www.e-t-a.de
1