SVS25 Datasheet, PDF (2/6 Pages) ETAL Group – Systematic integration of protection and distribution functions
Power distribution system SVS25
Technical data (Tamb = 25 °C, UB = DC 24 V)
Signalling
Rated voltage:
Total current
DC 24 V (18 ... 30 V)
max. 0.5 A
Signal terminal X41 for group signalling
Si 1
External supply + DC 24 V for aux. circuit
(max. 0.5 A)
Si 2
Output aux. circuit (max. 0.5 A)
Terminals:
2-pole screw terminals
push-in terminals max. 2.5 mm2
max. cable cross section
flexible with wire end ferrule
(with plastic sleeve)
0.25 – 1.5 mm2
flexible with wire end ferrule
(without plastic sleeve) 0.25 – 2.5 mm2
stripping length
8 mm
General data
Mounting of housing
Temperature range
Storage temperature
Housing material
Degree of protection
Insulation voltage
Dimensions
Mass
symmetrical rail to EN 60715 - 35 x 7.5
0...50 °C (without condensation)
-20...+70 °C
moulded
terminals
IP20 DIN 40050
printed circuit board IP00 DIN 40050
(double coating)
DC 250V (pcb)
see dimensions
(tolerances to DIN ISO 286 part 1 IT13)
SVS201-08-001
approx. 625 g
Mounting position
Notes for installation
l The max. total current of 40A per way must not be exceeded
l The user has to ensure that the cable cross section of the load
circuit in question complies with the current rating of the used
load or circuit protector.
l The technical data of the circuit protector have to be observed.
l In addition special precautions must be taken in the system or
machine (e.g. use of a safety PLC) which reliably prevent an
automatic re-start of parts of the system (cf. Machinery Directive
2006/42/EG and EN 60204-1, Safety of Machinery). In the event
of a failure (short circuit/overload) the load circuit will be discon-
nected by the circuit protector.
l The power distribution system must only be installed by qualified
personnel.
l It is only intended for use with safety extra-low voltage (= 24V DC).
l Only after expert installation must the device be supplied with
power.
l After tripping of the circuit protector, before reset, the cause of
6
short circuit or overload has to be remedied.
l The national standards (e.g. for Germany DIN VDE 0100) have
to be observed for installation and selection of feed and return
cables.
l Connection to a higher or not reliably disconnected voltage can
cause hazardous conditions or damages.