English
Language : 

SVS25 Datasheet, PDF (1/6 Pages) ETAL Group – Systematic integration of protection and distribution functions
Power distribution system SVS25
Description
The new power distribution system type SVS25 meets all requirements
of the automation technology with regard to reliably overcurrent
protection and optimised current distribution.
The track-mountable power distribution system SVS25 distributes the
voltage potentials supplied by a DC 24 V switch-mode power sup-
ply to 8 slots and selectively protects the connected loads by means
of the plugged in circuit protector type REF16-S101-DC24V. The
SVS25 simplifies wiring and distribution with a load current of 10A per
way and a max. total current of 40A in short-circuit-limited DC 24 V
applications. 10 protected »+« load outputs and 10 minus terminals per
slot help significantly reduce wiring time.
Any load circuit which might be disconnected due to overload or short
circuit generates a single signal which will be summarised in a group
signal directly on the power distribution system and which will be fed
back directly to the control unit.
The line entry for the DC 24 V supply as well as the load output
terminals are designed as push-in terminals so that the entire system
can be wired quickly and cost-effectively.
Technical data (Tamb = 25 °C, UB = DC 24 V)
Application:
Suitable for the following types:
Electronic
circuit protectors
REF16-S101
REF16-S100 (without signalling)
Modular power distribution system for short circuit current
limited DC 24 V applications
Supply
Rated voltage:
DC 24 V (18...30 V)
Features and Benefits
l Systematic integration of protection and distribution functions
l Power distribution and selective protection of
DC 24 V load circuits all in one
l Clearly laid-out distribution concept
l Profitability through considerably reduced wiring time
l Reduction of planning, design and installation time
l Ease of maintenance, diagnosis and system extension
l Compact power distribution for compact control cabinets
l 10 plus and minus terminals per slot
l Integral group signalling
Total current
max. 40 A
DC 24 V (+) = X21 1+ / 2+
DC 24 V (-) = X21 1- / 2-
Terminals
2 x 2-pole push-in terminals max. 10 mm2,
for power supplies
integral loop-through, for sub-wiring
cable cross section
flexible with wire end ferrule
(with plastic sleeve) 0.75 – 10 mm2
stripped length 18 mm
F-slots
8 slots for circuit protectors,
prepared for types REF16-S101-… / REF16-S100-…F1...F81) =
terminals X1....X8
Order numbering code
Load outputs, load output (+) and load output (-)
per way (X1...X8)
Rated voltage
DC 24 V (18...30 V)
Type
SVS25 power distribution system for REF16-S
l for short-circuit limited DC 24 V applications
l max. 40 A cont. load
l group signalling terminals X41 included,
DC24V / max. 0.5 A, has to be protected separately
Max. number of circuit protectors on the
distribution system
08 8 circuit protectors [F1 ...F8)
 Population, load output, minus and
signalling terminals
001 completely fitted with push-in terminals (max.
2.5 mm2, without wire end ferrule)
SVS25 08 - 001 ordering example
Current
Load terminals:
max. 10 A per terminal block (1 to 10)
10 x 1/2/3/4//5/6/7/8/9/10 protected per slots
F1...F81) led out to terminals X1.1...X8.1
Minus terminals:
10 x 1/2/3/4//5/6/7/8/9/10 protected per slots
F1...F81) led out to terminals X1.2...X8.2
Terminals:
push-in terminal block, 2 x 5-pole
max. cable cross section
6
flexible with wire end ferrule
(with plastic sleeve)
0.25 – 1.5 mm2
flexible with wire end ferrule
(without plastic sleeve) 0.25 – 2.5 mm2
stripping length
8 mm
Accessories: see page "accessories"
1646
1) When mounted side-by-side and fully equipped with the circuit protectors REF16-Sxxx
rated 10A the devices can only carry 80% of their rated load continuously.
www.e-t-a.de