English
Language : 

8340-G Datasheet, PDF (1/6 Pages) ETAL Group – Magnetic and Hydraulic-Magnetic Circuit Breaker
Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...
Description
Single and two pole magnetic circuit breakers with trip-free
mechanism and push/pull on/off manual actuation. A choice of fast
magnetic only or hydraulically delayed switching characteristics (S-
type MO or HM CBE to EN 60934) ensures suitability for a wide range
of applications. Convenient threadneck panel or plug-in mounting,
and with a white push button indicator band showing clearly the
tripped/off position. Available with auxiliary contacts (1 x N/O, 1 x
N/C) for status signalling.
Approved to CBE standard EN 60934 (IEC 60934).
Typical application
1
8340-G2...
Control equipment, communications systems, power semiconductors.
1-pole
2-pole
Standard current ratings and typical internal resistance values
Technical data
Current rating (A)
0.02
0.05
0.08
0.1
0.15
0.2
0.3
0.5
0.75
1
1.25
1.5
1.75
2
2.5
3
4
5
6
8
10
12
15
16
20
25
30
40
50
Internal resistance (Ω) per pole
-F4/-F5
-E1/H1/R1 -E2/H2/R2
583
94
35.8
23
9.9
5
2.44
0.79
0.39
0.25
0.15
0.10
0.083
0.059
0.044
0.028
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02*
< 0.02*
2441
376
148
94
39
30.5
9.9
3.16
1.55
0.79
0.58
0.37
0.30
0.20
0.146
0.10
0.059
0.040
0.026
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
2449
365
144
84
38
22.4
9.7
3.1
1.51
0.77
0.56
0.36
0.29
0.24
0.138
0.099
0.057
0.038
0.026
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
* 50 % ON duty / 60 min.
For further details please see chapter: Technical Information
Voltage rating
3 AC 415 V; AC 240 V, 50/60 Hz; DC 80 V
(higher DC voltages to special order)
Current ratings
0.02...50 A DC
0.02...30 A AC
Auxiliary circuit
1 A, AC 240 V/DC 65 V
0.5 A, DC 80 V
Typical life
3 AC 415 V, AC 240 V:
0.02...30 A
DC 80 V: 0.02...25 A
0.02...30 A
40 + 50 A
Ambient temperature
6,000 operations at 1 x IN, inductive
10,000 operations at 1 x IN, resistive
6,000 operations at 1 x IN, inductive
10,000 operations at 1 x IN, resistive
5,000 operations at 1 x IN, resistive
-40...+85 °C (-40...+185 °F)
Insulation co-ordination
(IEC 60664 and 60664A)
rated impulse
pollution
withstand voltage degree
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A)
operating area
test voltage AC 3,000 V
Line to Load
test voltage AC 1,500 V
pole to pole (2- and 3-pole) test voltage AC 1,500 V
main to auxiliary circuit test voltage AC 1,500 V
switching to trip circuit test voltage AC 1,500 V
(version -X)
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity
6 x IN at AC;
IEC 60934 - test sequence E 4 x IN at DC
Interrupting capacity
(UL 1077)
AC:
DC:
IN
1-pole
2-pole
1-pole
2-pole
0.02...20 A
AC 250 V/3,500A
AC 250 V/3,500A
0.02...50 A
0.02...30 A
25...30 A
AC 250 V/3,500A
AC 250 V/5,000A
DC 80 V/3,500 A
DC 80 V/3500 A
Degree of protection
(IEC 60529/DIN 40050)
operating area IP40
terminal area IP00
Vibration
with button down:
other mounting planes:
10 g (57-2000 Hz), ± 0.76 mm (10-57 Hz)
at 0.9 x IN
10 g (57-2000 Hz) at IN
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
100 g (11 ms) at 1 x IN, directions 1,2,3,4,5
100 g (11 ms) at 0.8 x IN, direction 6
to IEC 60068-2-27, test Ea
Corrosion
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass
approx. 70 g per pole
1646
www.e-t-a.de
1