English
Language : 

B84299C2160B003 Datasheet, PDF (6/21 Pages) EPCOS – Filters for Power Lines
Filters for power lines
16 to 150 A, 100 dB from 14 kHz
B84299*B003
B84299*E003
General technical data (continued)
Power dissipation
Capacitive reactive current/line
Max. permissible harmonic
distortion (THD)
Permissible ambient
temperature
Climatic category
(EN 60068-1)
Mechanical version
PD See characteristics
Ireactive See characteristics
At rated current IR
At 400/230 V and 50 Hz (typical
value)
8
% To EN 50160
TA 25/+40
°C
25/085/56
C
D
25 °C/+85 °C/56 days damp
heat test
Cable glands at both ends or
flexible connector fitting
Direct connection to shielding
wall
Characteristics and ordering codes
IR Mechanical
version
A
2-line filters
16 C
16 D
32 C
32 D
63 C
63 D
100 C
100 D
4-line filters
16 C
16 D
32 C
32 D
63 C
63 D
100 C
100 D
150 C
150 D
Rmax
mΩ
< 50
< 50
< 20
< 20
< 6.0
< 6.0
< 3.5
< 3.5
< 50
< 50
< 20
< 20
< 6.0
< 6.0
< 3.5
< 3.5
< 2.0
< 2.0
PD
Ireactive Dimensional Page Approx. Ordering code
drawing
weight
WA
kg
< 30 1.2 1
< 30 1.2 2
< 40 2.7 3
< 40 2.7 4
< 50 4.9 5
< 50 4.9 6
< 70 6.5 7
< 70 6.5 8
7 12
8 12
9 20
10 20
11 36
12 36
13 60
14 60
B84299C2160B003
B84299D2160B003
B84299C2320B003
B84299D2320B003
B84299C1630B003
B84299D1630B003
B84299C1101B003
B84299D1101B003
< 30 1.2 9
< 30 1.2 10
< 40 2.7 11
< 40 2.7 12
< 70 4.9 5
< 70 4.9 6
< 100 6.5 7
< 100 6.5 8
< 140 6.5 13
< 140 6.5 14
15 24
16 24
17 30
18 30
11 40
12 40
13 60
14 60
19 95
20 95
B84299C2160E003
B84299D2160E003
B84299C2320E003
B84299D2320E003
B84299C1630E003
B84299D1630E003
B84299C1101E003
B84299D1101E003
B84299C1151E003
B84299D1151E003
6