English
Language : 

B84299C2160B003 Datasheet, PDF (5/21 Pages) EPCOS – Filters for Power Lines
Filters for power lines
16 to 150 A, 100 dB from 14 kHz
Insertion loss αe (typical values at Z = 50 Ω)
B84299*B003
B84299*E003
Asymmetrical measurement circuit
to MIL-STD-220A
General technical data
Rated voltage
2-line filters
Rated voltage
4-line filters
Rated frequency
Rated current
Maximum admissible
overcurrent
Test voltage
Voltage drop/phase
Maximum DC resistance
VR 250
V Line/line
Line/case
VR 440
250
V Line/line
V Line/case
fR
50/60
Hz
See characteristics Referred to +40 °C ambient
temperature
Iover 75  IR for 50 ms
10  IR for 1 s
2  IR for 1 min
1.4  IR for 15 min
Vtest 1200 VDC, 2 s
1200 VDC, 2 s
Line/line
Line/case
∆V <1
% Of VR at 50 Hz and IR
Rmax See characteristics Per line
5