EMC Characteristics (5)
Conducted emissions
Harmonic current correction
ESD  air
ESD contact
Radiated immunity
Fast transients
Surge
Conducted immunity
General Specifications
Hold-up time
Efficiency
Isolation voltage
Weight
MTBF (@25º C)
EN55022, FCC part 15
EN61000-3-2
EN61000-4-2
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
850 Vac @ 60 Hz
115 Vac @ 150 W
230 Vac @ 150 W
Input/output
Input/chassis
260g (9.2 oz)
Telcordia SR-332
MIL-HDBK-217F
Level B
Compliant
Level 3
Level 3
Level 3
Level 3
Level 3
Level 3
20 ms @ 150 W
81% typ.
84% typ.
4000 Vac
1500 Vac
900,000 hours min.
350,000 hours min.
Embedded Power for
Business-Critical Continuity
Rev.12.23.08_140
TLP150-M Series
 of 4
Environmental Specifications
Thermal performance
Relative humidity
Altitude
Vibration (See Note 7)
Shock
Operating ambient,
(See derating curve)
Non-operating
0 °C to 50 °C ambient,
200 LFM forced air
0 °C to 50 °C ambient,
convection cooled
50 °C to 70 °C ambient,
convection cooled
Non-condensing
Operating
Non-operating
5-500 Hz
per MIL-STD-810E
0° C to +70 °C
-40 °C to +85 °C
150 W
100 W
Derate linearly to 50% load
5-95% RH
10,000 feet max.
30,000 feet max.
2.4 G rms peak
516.4 Part IV