English
Language : 

LPT100-M Datasheet, PDF (2/3 Pages) Emerson Network Power – 130 Watts Medical and ITE safeties
Embedded Power for
Business-Critical Continuity
Environmental Specifications
Operating temperature:
Storage temperature:
Electromagnetic
susceptibility:
Humidity:
Vibration:
MTBF calculated:
0° to 50 °C ambient derate each output as 2.5% per degree from 50° to 70 °C. -20 °C start up
-40 °C to +85 °C
designed to meet EN61000-4;
-2, -3, -4, -5, -6, -8, -11 Level 3
Operating; non-condensing 10% to 90% RH, non-operating, non-condensing 10% - 95%
IEC68-2-6 to the levels of IEC721-3-2
583,000 hours at full load and 25 °C ambient conditions. 230 Vac input, Bellcore
Rev. 10.9.09_141
LPT100-M Series
 of 3
Mechanical Drawing
GND
Output Voltage
Adjust Pots
SK3
PIN 1 (LIVE)
PIN 3 (NEUTRAL)
SK1
3.73”
(94.6)
4.00”
(101.6)
SK2
Output Voltage
Adjust Pots
Mounting Hole
ø0.16” [4.0] 4 Places
Max. Screw Head
Diameter .22” (5.6)
0.197” (5.0) Minimum
Standoff height