English
Language : 

LPT100-M Datasheet, PDF (1/3 Pages) Emerson Network Power – 130 Watts Medical and ITE safeties
Embedded Power for
Business-Critical Continuity
LPT100-M Series
130 Watts
Total Power:
Input Voltage:
# of Outputs:
80 - 130 Watts
90 - 264 Vac
Triple
Rev. 10.9.09_141
LPT100-M Series
 of 3
Special Features
• Medical and ITE safeties
• Active power factor correction
• 2” x 4” footprint
• Less than 1U high
• EN61000-3-2 compliant
• Remote sense
• Power fail
• Adjustable main output
• Built-in Class B EMI filter
• Overvoltage protection
• Overload protection
• Thermal overload protection
• LPX50 enclosure kit available
Safety
• TUV 60950, 60601-1
• UL
60950, 60601-1
• CSA
60950, 60601-1
• NEMKO 60950, 60601-1
• AUSTEL 60950, 60601-1
• CB
Certificate & report
• CE
Mark (LVD)
Electrical Specifications
Input
Input ra­nge:
Frequency:
Inrush current:
Efficiency:
EMI/RFI:
Safety ground
leakage current:
90 - 264 Vac; 127 - 300 Vdc
47 - 63 Hz
50 A max., cold start @ 25 °C
82% typical at full load
FCC Class B conducted; CISPR22 Class B conducted;
EN55022 Class B conducted; VDE0878PT3 Class B conducted
275 µA @ 50/60 Hz, 264 Vac input
Output
Maximum power:
80 W for convection;
130 W with 200 LFM forced air
Adjustment range:
Hold-up time:
All outputs adjustable - 40%, +10%, except for +24V output on LPT104-M
which will be -10%, +20% and 3.3 V output on the LPT101-M +10%, -15%
10 ms @ 130 W load, 120 Vac input
Overload protection: Short circuit protection on all outputs. Case overload
protected @ 110 - 160% above rating for V1 & V2, 110-190% for V3
Overvoltage protection: 15 - 35% above nominal output
Logical Control
Power failure:
Remote sense:
Active LowTTL logic signal goes high 100 - 500 msec after main output; it
goes low at least 6 msec before loss of regulation
Compensates for 0.5 V lead drop min. Will operate without remote sense
connected. Reverse connection protected.