English
Language : 

LPS60-M Datasheet, PDF (2/3 Pages) Emerson Network Power – Medical safety approvals
Environmental Specifications
Operating temperature: 0° to 50°C ambient derate each output as 2.5%
per degree from 50° to 70°C, -20°C startup
Storage temperature: -40°C to +85°C
Electromagnetic
susceptibility:
Humidity:
designed to meet IEC801, -2, -3, -4, -5, -6, Level 3
Operating; non-condensing 5% to 95% RH
Vibration:
Three orthogonal axes, sweep at 1cot/min, 5 min.
dwell at four major resonances 0.75G peak 5Hz to
500Hz, operational
Temperature coefficient ±0.04% per °C
MTBF demonstrated
>550,000 hours at full load and 25°C ambient
conditions
Mechanical Drawing
0.22"
(5.6)
GND
M1
3.00"
(76.2)
2.55"
(64.8)
SK 1
1N
3L
0.22"
(5.6)
4.56"
(115.8)
5.00"
(127)
Rev. 07.23.07
LPS60-M Series
2 of 3
80W
60W
Output
Power
(Watts) 40W
20W
Power Derating Curve
30 CFM Forced Air Cooling
Natural
Convection
Cooling
40W
30W
0W
0°C 10°C 20°C 30°C 40°C 50°C 60°C 70°C
TA – Ambient Temperature – °C
M2
SK201 _+
Remote Sense
Connector
Voltage
Adj. Pot
SK 2
1
2
3
4
5
6
0.15" (4)
DIA (4 places)
1.69"
(42.9)
0.12"
(3)