Environmental Specifications
Operating temperature:
0° to 50 °C ambient derate each output as 2.5% per degree from
50° to 70 °C. -20 °C start up
Storage temperature:
Electromagnetic
susceptibility:
Humidity:
-40 °C to +85 °C
Designed to meet EN61000-4;
-2, -3, -4, -5, -6, -8, -11 Level 3
Operating; non-condensing 10% to 95% RH
Vibration:
IEC68-2-6 to the levels of IEC721-3-2
MTBF demonstrated
> 550,000 hours at full load and 25 °C ambient conditions
Mechanical Drawing
M1
GND
SK1 1
3
VR1
Output Voltage
Adjust Pot M2
14
8
14
SK5
1
SK203
SK2
3.73"
(94.7)
4.00"
(101.6)
Mounting Hole
Ø0.16"[4.0] 4 Places
Max. Screw Head
Diameter .22” (5.6)
Rev. 4.30.09_29
LPS100-M Series
 of 3
0.197” (5.0) Minimum Standoff Height