English
Language : 

LPS100-M_09 Datasheet, PDF (1/3 Pages) Emerson Network Power – 150 Watts Medical and ITE safeties
Embedded Power for
Business-Critical Continuity
LPS100-M Series
150 Watts
Total Power:
Input Voltage:
# of Outputs:
80 - 150 Watts
90 - 264 Vac
Single
Rev. 4.30.09_29
LPS100-M Series
 of 3
Special Features
• Medical and ITE safeties
• Active power factor correction
• 2” x 4” footprint
• Less than 1U high
• EN61000-3-2 compliant
• Remote sense
• Power fail
• Adjustable main output
• Built-in Class B EMI filter
• Overvoltage protection
• Overload protection
• Thermal overload protection
• Isolated12 V Fan output
• LPX50 Enclosure kit available
Safety
• TUV 60950, 60601-1
• UL
60950, 60601-1
• cULus
60950, 60601-1
• TUV 60950, 60601-1
• CB
Certificate & report
• CE
Mark (LVD)
Electrical Specifications
Input
Input ra­nge:
Frequency:
Inrush current:
Efficiency:
EMI/RFI:
Safety ground
leakage current:
90 - 264 Vac; 120 - 300 Vdc
47-63 Hz
50 A max., cold start @ 25 °C
88% typical at full load
FCC Class B conducted; CISPR22 Class B conducted;
EN55022 Class B conducted; VDE0878PT3 Class B conducted
275 µA @ 50/60 Hz, 264 Vac input
Output
Maximum power:
100 W for convection (80 W for LPS102-M);
150 W with 30 CFM forced air (120 W for LPS102-M)
Adjustment range:
Fan output:
± 10% minimum on the main outputs
12 V @ 1 A isolated, ± 10%
Hold-up time:
10 ms @ 150 W load, 120 Vac input
Overload protection: Short circuit protection on all outputs. Case overload
protected @ 110-160% above rating
Overvoltage protection: 15-35% above nominal output
Logical Control
Power failure:
Open collector logic signal goes high 100-500 msec after main output; it
goes low at least 6 msec before loss of regulation
Remote sense:
Compensates for 0.5 V lead drop min. Will operate without remote sense
connected. Reverse connection protected.