English
Language : 

HBGCMP Datasheet, PDF (4/8 Pages) Dialight Corporation – DuroSite® Series LED High Bay
DuroSite® LED High Bay Fixture Options
Occupancy Sensor Version
Mechanical, Electrical and Photometric information is the same
as on page 3 except where detail is provided
Fixture Weight:
Container Weight:
Sensor Mounting:
19lbs (11.34kg)
25lbs (8.62kg)
Attached to the base of the neck using
a semi-rigid flexible conduit
Occupancy Sensor:
Dry location Leviton OSFHU - CTW (120 - 347V AC)
or C4W (480V AC)
Wet location Wattstopper HB350W (120 – 347V AC)
or HB340W (480V AC)
Sensor Timing:
30 seconds to 20 minutes
Sensor Lens Options: Comes complete with interchangeable lenses
for multiple mounting heights
Operating Temperature
Leviton models:
-14°F to +149°F (-10°C to +65°C)
Wattstopper models: -40°F to +149°F (-40°C to +65°C)
Features and Benefits
• No additional electrical connections required for installation
Dimensions in Inches [mm]
• Flexible conduit permitting the positioning of the occupancy senso
for optimal coverage
• Interchangeable sensor lens for high bay, low bay, or aisle
applications
Variable Dimming (0-10 VDC) & STEP Dimming
8.00
(203,2)
1/4” - 20 SELF - TAPPING
SCREW HOLE (6)
5/16” - 18 X .75”
THREADED HOLE (2)
10’ (3.05m)
DIMMIMG CABLE
10’ (3.05m)
Power Cord
1.91
(48,6)
Ø 16.0
(406)
3.13
(79,4)
Dimensions in Inches [mm]
Mechanical, Electrical and Photometric information is the same
as on page 3 except where detail is provided
Variable Dimming Cable: Two conductor cable
Power Cable:
Three conductor cable
Dimming Cable Position: Side of the neck through a cable gland
Variable Dimming Control: 0-10 V DC active
Dimming Range:
10 V DC = 100% light output
0 V DC = 15% light output
Features and Benefits
• 10’ plenum rated dimming control cable pre-installed
• Dimming cabling independent of fixture wiring
• Multiple High Bays can be connected to the same dimmer
• May also be configured to operate in a single STEP Dimming
configuration
STEP Dimming Mode
The variable dimming High Bays may also be configured to operate
in a single STEP Dimming configuration. When the dimming control
conductors are connected together, the light output will be reduced
to approximately 15% of the maximum light output. The total fixture
power consumption will also be reduced to approximately 20% (30
W). Connecting the leads together can be accomplished with a
common wall switch.
4