DRP012V015W1AY Datasheet, PDF (8/12 Pages) Delta Electronics, Inc. – CliQ DIN Rail Power Supply
TECHNICAL DATASHEET
CliQ DIN Rail Power Supply
12V 15W 1 Phase / DRP012V015W1A□
Safety Instructions
– ALWAYS switch mains of input power OFF before connecting and
disconnecting the input voltage to the unit. If mains are not turned OFF,
there is risk of explosion / severe damage.
– To guarantee sufficient convection cooling, keep a distance of
50mm above and below the device as well as a lateral distance of
20mm to other units.
– Note that the enclosure of the device can become very hot depending on
the surrounding air temperature and load of the power supply. Risk of
burns!
– Only plug in and unplug connectors when power is turned off!
– DO NOT insert any objects into the unit.
– Hazardous voltages may be present for up to 5 minutes after the input
mains voltage is disconnected. Do not touch the unit during this time.
– The power supplies unit should be installed in minimum IP54 rated
enclosure.
– The power supplies are built in units and must be installed in a cabinet or
room (condensation free environment and indoor location) that is
relatively free of conductive contaminants.
Functions
■ Graph illustrating the Start-up Time, Rise Time, and Hold-up Time
Start-up Time
The time required for the output voltage to reach 90% of its set value, after the input voltage is applied.
Rise Time
The time required for the output voltage to change from 10% to 90% of its set value.
Hold-up Time
Hold up time is the time when the AC input collapses and output voltage retains regulation for a certain period of time. The time required
for the output to reach 95% of its set value, after the input voltage is removed.
8
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 03)