English
Language : 

DRP012V015W1AY Datasheet, PDF (4/12 Pages) Delta Electronics, Inc. – CliQ DIN Rail Power Supply
TECHNICAL DATASHEET
CliQ DIN Rail Power Supply
12V 15W 1 Phase / DRP012V015W1A□
Safety Standards / Directives
Electronic Equipment in Power Installations
Electrical Safety
Industrial Control Equipment
Hazardous Location / ATEX (For DRP012V015W1AY)
II 3G ATEX 94/9/EC; (For DRP024V060W1BA)
IECEX Test Report
CE
EN50718 / IEC62103
TUV Bauart to EN60950-1, UL/cUL recognized to
UL60950-1, CSA C22.2 No. 60950-1, CB scheme to
IEC60950-1
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01,
CSA to CSA C22.2 No. 107.1-01
cCSAus to CSA C22.2 No.213-M1987, ANSI / ISA
12.12.01:2007 Class I, Division 2, Group A,B,C,D T4
EN60079-0:2009, EN60079-15:2010
( II 3GII 3G Ex nA IIC T4 Gc)
Certificate No. EPS 12 ATEX 1 491 X
For IEC60079-0, IEC60079-15
In conformance with EMC Directive 2004/108/EC and
Low Voltage Directive 2006/95/EC
Material and Parts
Galvanic Isolation
Input to Output
Input to Ground
Output to Ground
For DRP012V015W1AY:
In conformance with Equipment for explosive
atmospheres (ATEX) directive 94/9/EC
RoHS Directive 2011/65/EU Compliant
4.0KVac
1.5KVac
1.5KVac
EMC
EMC / Emissions
Immunity to
Electrostatic Discharge
Radiated Field
Electrical Fast Transient / Burst
Surge
Conducted
Power Frequency Magnetic Fields
Voltage Dips
Low Energy Pulse Test (Ring Wave)
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)
CISPR22, EN55022, EN55011, FCC Title 47: Class B
EN61000-4-2
EN61000-4-3
EN61000-4-4
IEC6100-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
IEC61000-4-12
Level 4 Criteria A1)
Air Discharge: 15kV
Contact Discharge: 8kV
Level 3 Criteria A1)
80MHz–1GHz, 10V/M with 1kHz tone / 80% modulation
Level 3 Criteria A1)
2kV
Level 3 Criteria A1)
Common Mode2): 2kV
Differential Mode3): 1kV
Level 3 Criteria A1)
150kHz-80MHz, 10Vrms
Level 3 Criteria A1)
10A/Meter
Level 3 Criteria A1)
100% dip; 1 cycle (20ms); Self Recoverable
Level 3 Criteria A1)
Common Mode2): 2kV
Differential Mode3): 1kV
4
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 03)