TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 120W 1 Phase / DRP024V120W1B□
De-rating
Fig. 1.1 De-rating for Vertical and Horizontal Mounting Orientation
> 50°C de-rate power by 2.5% / °C
Output De-rating VS. Input Voltage
Note
1. Power supply components may degrade, or be
damaged, when the power supply is
continuously used outside the shaded region,
refer to the graph shown in Fig. 1.1.
2. If the output capacity is not reduced when
surrounding air temperature >50°C, the device
will run into Over Temperature Protection.
When activated, the output voltage will go
into bouncing mode and will recover when the
surrounding air temperature is lowered or the
load is reduced as far as necessary to keep
the device in working condition.
3. If the device has to be mounted in any other
orientation, please do not hesitate to contact
info@deltapsu.com for more details.
4. In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance of 20mm with adjacent units
while the device is in operation.
5. Depending on the surrounding air temperature
and output load delivered by the power
supply, the device housing can be very hot!
■No output power de-rating across the entire input
voltage range
Assembly & Installation
7
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 03)