English
Language : 

IMA-1000 Datasheet, PDF (6/14 Pages) Delta Electronics, Inc. – Safety rated for Medical, Industrial and IT
IMA-x1000 Power Supply Series
EMC
Radiated emissions 1)
Conducted emissions 1)
Power line harmonics
Voltage flicker
ESD
Radiated immunity
Electrical fast transient
Surge immunity
Conducted RF immunity
Power frequency magnetic field
Voltage dips and sags
Ring wave
Voltage fluctuations
IMA-x1000-xx
Applied standards
EN 55011, EN 55022 and FCC, Class B
EN 55011, EN 55022 and FCC, Class B
EN 61000-3-2, Class A
EN 61000-3-3
EN 61000-4-2, level 4, 8 kV contact, 15 kV air
EN 61000-4-3, level 2, 3 V/m
EN 61000-4-4, level 3, ±2 kV
EN 61000-4-5, level 3, 1 kV DM, 2 kV CM
EN 61000-4-6, level 2, 3 Vrms
EN 61000-4-8, level 2, 3 A/m
EN 61000-4-11, 30%, 500 ms
EN 61000-4-11, 60%, 100 ms
EN 61000-4-11,100%, 10 ms
EN 60601-1-2, 30%, 500 ms
EN 60601-1-2, 60%, 100 ms
EN 60601-1-2, 100%, 10 ms
EN 60601-1-2, 100%, 5000 ms
EN 61000-4-12, level 3, 1 kV DM, 2 kV CM
EN 61000-4-14, Class 3
Criteria
A
A
A
A
A
A
A
B
A
A
B
A
B
A
A
1) Power Supply Unit inside a dummy system
Safety standards and directives 1)
IEC/EN 60950-1, Edition 2 and all national devia-
tions
IEC/EN 60601-1, Edition 3 (tested against Edition
2, too) and all national deviations
Protection class
IMA-x1000-xx
UL 60950-1/CSA 22.2 No 60950-1, Edition 2;
5000 m (16,400 ft) altitude, 120 V to 300 Vdc and 100 V to 240 ±10% Vac
(UL File E191395)
IEC 60601-1(2005), EN60601-1(2006)
ANSI/AAMI ES 60601-1(2005)
CAN/CSA C22.2 No. 60601-1 (2008);
3,000 m (9,800 ft) altitude, 100 V to 240 Vac ±10% (UL File E325662)
I
1) Designed to support Type B Applied Part End Product Requirements
Ecological characteristics
IMA-x1000-xx
Waste Electrical and Electronic Equipment Directive (WEEE) 2002/96/EC
RoHS - EU DIRECTIVE 2011/65/EC RoHS compliancy
6