TECHNICAL DATASHEET
Sync DIN Rail Power Supply
24V 100W Series / DRS-24V100W1A□ / DRS-24V100W1N□
Model Number
DRS-24V100W1A☐
DRS-24V100W1N☐
EMC
EMC / Emissions
Component Power Supply for General Use
Immunity to
Electrostatic Discharge
Radiated Field
Electrical Fast Transient / Burst
Surge
Conducted
Power Frequency Magnetic Fields
Voltage Dips and Interruptions
Low Energy Pulse Test (Ring Wave)
Harmonic Current Emission
Voltage Fluctuation and Flicker
Generic Standards: EN 61000-6-3, EN 61000-6-4
CISPR 22, EN 55022 EN 55011, FCC Title 47: Class B
EN 61204-3
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
Generic Standards: EN 55024, EN 61000-6-1, EN 61000-6-2
Level 3 Criteria A1)
Air Discharge: 8kV
Contact Discharge: 6kV
Level 3 Criteria A1)
80MHz-1GHz, 10V/M with 1kHz tone / 80% modulation
1.4GHz-2GHz, 3V/M with 1kHz tone / 80% modulation
2GHz-2.7GHz, 1V/M with 1kHz tone / 80% modulation
Level 3 Criteria A1)
2kV
Level 3 Criteria A1)
Common Mode3): 2kV
Differential Mode4): 1kV
Level 3 Criteria A1)
150kHz-80MHz, 10Vrms
IEC 61000-4-8 Criteria A1)
30A/Meter
IEC 61000-4-11
IEC 61000-4-12
0% of 100Vac, 20ms
0% of 100Vac, 5000ms
40% of 100Vac, 200ms
70% of 100Vac, 10ms
70% of 100Vac, 500ms
0% of 240Vac, 20ms
0% of 240Vac, 5000ms
40% of 240Vac, 200ms
70% of 240Vac, 500ms
Level 3 Criteria A1)
Common Mode3): 2kV
Differential Mode4): 1kV
Criteria A1)
Criteria B2)
Criteria B2)
Criteria A1)
Criteria A1)
Criteria A1)
Criteria B2)
Criteria A1)
Criteria A1)
IEC/EN 61000-3-2, Class A
IEC/EN 61000-3-3
1) Criteria A: Normal performance within the specification limits
2) Criteria B: Temporary degradation or loss of function which is self-recoverable
3) Asymmetrical: Common mode (Line to earth)
4) Symmetrical: Differential mode (Line to line)
5
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (March 2016, Rev. 00)