English
Language : 

DRS-24V100W1AX Datasheet, PDF (3/15 Pages) Delta Electronics, Inc. – Sync DIN Rail Power Supply
TECHNICAL DATASHEET
Sync DIN Rail Power Supply
24V 100W Series / DRS-24V100W1A□ / DRS-24V100W1N□
Mechanical
Case Cover / Chassis
Dimensions (L x W x D)
Unit Weight
Indicator
Cooling System
Terminal
Wire
Mounting Rail
Noise (1 Meter from power supply)
Model Number
DRS-24V100W1A☐
DRS-24V100W1N☐
Input
Output
Input / Output
Plastic
75 x 45 x 100 mm (2.95 x 1.77 x 3.94 inch)
0.325 kg (0.72 lb)
Green LED (DC OK)
Convection
3 Pins (Rated 300V/16A)
DRS-24V100W1☐Z: 4 Pins (Rated 300V/16A)
DRS-24V100W1☐R: 6 Pins (Rated 300V/16A)
AWG 22-12 / AWG 20-12
Standard TS35 DIN Rail in accordance with EN 60715
Sound Pressure Level (SPL) < 25dBA
Environment
Surrounding Air Temperature
Power De-rating
Operating Humidity
Operating Altitude
Shock Test
Vibration
Pollution Degree
Operating -20°C to +70°C (Cold start at -40°C @ 40% load)
Storage -40°C to +85°C
-10°C to -20°C de-rate power by 2% / °C
> 55°C de-rate power by 3.33% / °C
5 to 95% RH (Non-Condensing)
0 to 2,000 Meters (6,560 ft.)
Non-Operating IEC60068-2-27, Half Sine Wave: 50G for a duration of 11ms;
3 times per direction, 9 times in total
Operating IEC 60068-2-27, Half Sine Wave: 10G for a duration of 11ms;
1 time in X axis
Non-Operating IEC 60068-2-6, Random: 5-500Hz; 2.09Grms, 20 min per axis
for all X, Y, Z directions
Operating IEC 60068-2-6, Sine Wave: 10-500Hz; 2G peak; displacement
of 0.35mm; 1 octave per min; 60 min per axis for all X, Y, Z
directions
2
Protections
Overvoltage
Overload / Overcurrent
Over Temperature
Short Circuit
Internal Fuse
Degree of Protection
Protection Against Shock
*PE: Primary Earth
< 34.8V, SELV Output, Latch Mode
105~140% of rated load current,
Fold Forward Mode (current rises, voltage drops),
Auto-recovery when the fault is removed
< 75°C Surrounding Air Temperature @ 100% load,
Latch Mode
Hiccup Mode, Non-Latching
(Auto-recovery when the fault is removed)
T3.15A
IP20
Class I with PE* connection
3
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (March 2016, Rev. 00)