English
Language : 

DRP012V015W1AX Datasheet, PDF (5/12 Pages) Delta Electronics, Inc. – Universal AC input voltage
TECHNICAL DATASHEET
CliQ DIN Rail Power Supply
12V 15W 1 Phase / DRP012V015W1A□
EMC
EMC / Emissions
Immunity to
Electrostatic Discharge
Radiated Field
Electrical Fast Transient / Burst
Surge
Conducted
Power Frequency Magnetic Fields
Voltage Dips
Low Energy Pulse Test (Ring Wave)
Voltage Fluctuation and Flicker
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
IEC 61000-4-12
CISPR 22, EN 55022, CISPR 11, EN 55011,
FCC Title 47: Class B
EN 55024, EN 61000-6-1, EN 61000-6-2
Level 4 Criteria A1)
Air Discharge: 15kV
Contact Discharge: 8kV
Level 3 Criteria A1)
80MHz-1GHz, 10V/M, 80% modulation (1kHz)
1.4GHz-2GHz, 3V/M, 80% modulation (1kHz)
2GHz-2.7GHz, 1V/M, 80% modulation (1kHz)
Level 3 Criteria A1)
2kV
Level 3 Criteria A1)
Common Mode2): 2kV
Differential Mode3): 1kV
Level 3 Criteria A1)
150kHz-80MHz, 10Vrms
Criteria A1)
30A/Meter
100% dip; 1 cycle (20ms); Self Recoverable
Level 3 Criteria A1)
Common Mode2): 2kV
Differential Mode3): 1Kv
IEC/EN 61000-3-3
5
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (April 2015, Rev. 04)