English
Language : 

DRS-24V30W1AZ Datasheet, PDF (3/11 Pages) Delta Electronics, Inc. – Sync DIN Rail Power Supply
TECHNICAL DATASHEET
Sync DIN Rail Power Supply
24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1AZ
Environment
Surrounding Air Temperature
Power De-rating
Operating Humidity
Operating Altitude
Shock Test (Operating)
Vibration (Operating)
Pollution Degree
Protections
Overvoltage
Overload / Overcurrent
Over Temperature
Short Circuit
Degree of Protection
Protection Against Shock
*PE: Primary Earth
Reliability Data
MTBF
Expected Cap Life Time
Operating -20°C to +70°C
Storage -40°C to +85°C
-10°C to -20°C de-rate power by 5% / °C
> 55°C de-rate power by 3.33% / °C
5 to 95% RH (Non-Condensing)
0 to 2,000 Meters
IEC 60068-2-27, Half Sine Wave: 10G for a duration of
11ms, 1 shock for X direction
IEC 60068-2-6, Sine Wave: 10-500Hz @ 19.6m/S² (2G
peak); 10 min per cycle, 60 min for X direction
2
< 34.8V, SELV Output, Auto-Recovery
110-150% of rated load current, Hiccup Mode,
Non-Latching (Auto-Recovery when the fault is
removed)
Auto-Recovery
Auto-Recovery when the fault is removed
IP20
Class I with PE* connection
> 700,000 hrs. as per Telcordia SR-332
I/P: 100Vac, O/P: 100% load, Ta: 35°C
10 years (230Vac, 50% load @ 40°C)
3
All parameters are specified at 25°C ambient unless otherwise indicated.
www.DeltaPSU.com (March 2015, Rev. 00)