English
Language : 

DRR-20X Datasheet, PDF (3/8 Pages) Delta Electronics, Inc. – CliQ II Redundancy Module
TECHNICAL DATASHEET
CliQ II Redundancy Module
20A, 40A / DRR-20□, DRR-40□
General Data
Isolation Voltage
Input / PE
Output / PE
Degree of Protection
Class of Protection
MTBF
Type of Housing
Dimensions (L x W x H)
Weight
LED (DC Input OK)
Test / Routine Test
Test / Routine Test
1.5 KVAC / 1.5 KVAC
1.5 KVAC / 1.5 KVAC
IP20
Class II with PE Connection
> 800,000hrs. as per BELL CORE STD or IEC61709
Aluminium (AL1100F)
121 x 50 x 122.1 mm
0.375 Kg
0.515 Kg
Vin1 OK and Vin2 OK (Green LED)
Climatic Data
Surrounding Air Temperature
Power De-rating
Operating Humidity
Shock Test (Non-Operating)
Vibration (Non-Operating)
Pollution Degree
Climatic Class
Operating
Storage
-40°C to +80°C
-40°C to +85°C
> 50% of Full load @ 70°C derated Linearly
< 95% RH (Non-Condensing)
IEC60068-2-27, 30G (300m/s2) for duration 18ms 1
Shock in 2 Directions tested with Fixture with EUT
mounted on DINRAIL in Vertical and Horizontal
position.
10Hz to 500Hz @ 30 m/S2 (3G peak); displacement of
0.35mm; 60min per axis for all X, Y, Z direction. Refer
to IEC 60068-2-6. Note: all
2 according to EN50178
3K3 according to EN 60721
EMC (Electromagnetic Compatibility)
Immunity to interference :
According to EN 61000-6-2
EN 61000-4-2 1)
Discharge of static electricity (ESD)
Housing:
Contact discharge:
Air Discharge:
EN 61000-4-3 1)
Radiate Field Immunity Housing:
Frequency/Field intensity:
EN 61000-4-8 2)
Power frequency magnetic fields Input:
Current:
CE (EMC and Low Voltage Directive)
Level 4
8 KV
15 KV
Level 3
80MHz - 1GHz / 10V/M with 1kHz tone / 80%
modulation
Level 3
10A /Meter
EN55011 corresponds to CISPR11 / EN55022 corresponds to CISPR22 / EM 61000 corresponds to IEC 1000
1) Criterion A: Normal operating behavior within the defined limits.
2) Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
3) Symmetrical: Conductor to conductor.
4) Asymmetrical: Conductor to ground.
5) Class B: Area of application industry and residential.
3
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (October 2013, Rev. 01)