English
Language : 

DRR-20X Datasheet, PDF (2/8 Pages) Delta Electronics, Inc. – CliQ II Redundancy Module
TECHNICAL DATASHEET
CliQ II Redundancy Module
20A, 40A / DRR-20□, DRR-40□
Specifications
Input Data
Redundancy Module
Nominal Input Voltage
Input Voltage Range
Nominal Current
Input Voltage Alarm / Relay Contacts
DRR-20□
24-48Vdc
DRR-40□
22-60Vdc
20A max
40A max
24V system:
both Vin1 & Vin2 >18V
± 5% or
<30V max. relay contacts
48V system:
both Vin1 & Vin2 >36V
± 5% or
<60V max. relay contacts
Note: The LED will turn on when The Vin1 & Vin2 > 18V ±5% (For 24V system) or > 36V ±5% (For 48V system) and not more than 30V
(For 24V system) or not more than 60V (For 48V system), The relay contacts will be closed. If Vin1 & Vin2 is under or over this range,
The LED will be turn off.
Output Data
Nominal Output Voltage / Tolerance
Vin-0.65V (Typ)
Nominal Current
20A max / 40A max
Derating above +50 °C
> 50°C (2.5% / K.)
Short Circuit / Over Load Limit
<25A for DRR- 20A)
<50A for DRR-40A
Note: The overload condition must be controlled by The PSUs in parallel; The limit of input current would not more than 25A (For 20A
module) or not more than 50A (For 60A module).
Efficiency
> 97% typical.
Certification / Standards
Electrical Equipment of Machines
Electrical Safety (Information Technology Equipment)
Industrial Control Equipment
Hazardous location / ATEX (For DRR-20A and DRR-40A)
IEC60204-1 (Over Voltage Category III)
UR/cUR recognized to UL60950-1, SIQ BG to
EN60950-1, CB test certificate and report to
IEC60950-1 and CE.
UL/cUL recognize to UL508
cCSAus to CSA C22.2 No.213-M1987, ANSI / ISA
12.12.01:2007 [Class I, Division 2, Group A,B,C,D T4,
Ta = -40°C to +80°C (> +50°C derating)]
II 3G ATEX 94/9/EC (For DRR-20A and DRR-40A)
CE
Electronic equipment for use in electrical power installations
Safety Entry Low Voltage
RoHS Compliant
Protection Against Electric Shock
EN60079-0:2009, EN60079-15:2010[ II 3G Ex nA nC
IIC T4 Gc, Ta = -40°C to +80°C (> +50°C derating)]
Certificate No. EPS 12 ATEX 1 491 X
Conformance with EMC guideline
2004/108/EC and for low voltage guideline 2006/95/EC
For DRR-20A and DRR-40A:
In conformance with Equipment for explosive
atmospheres (ATEX) directive 94/9/EC
EN50178 / IEC62103
PELV (EN60204), SELV (EN60950)
RoHS Directive 2011/65/EU Compliant
DIN 57100-410
2
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (October 2013, Rev. 01)