English
Language : 

PMH-24V150WCBX Datasheet, PDF (2/13 Pages) Delta Electronics, Inc. – PMH Panel Mount Power Supply
TECHNICAL DATASHEET
PMH Panel Mount Power Supply
24V 150W 1 Phase / PMH-24V150WCB□
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
Input Voltage Range
Nominal Input Frequency
Input Frequency Range
DC Input Voltage Range*
Input Current
Efficiency at 100% Load
Max Inrush Current (Cold Start)
Power Factor at 100% Load
Leakage Current
100-240Vac
85-264Vac
50-60Hz
47-63Hz
120-375Vdc
< 1.60A @ 115Vac, < 0.90A @ 230Vac
> 89.0% @ 115Vac, > 91.0% @ 230Vac
< 30A @ 115Vac, < 60A @ 230Vac
> 0.98 @ 115Vac, > 0.89 @ 230Vac
< 0.9mA @ 264Vac
*Fulfills test conditions for DC input. Safety approval for DC input can be obtained upon request.
Output Ratings / Characteristics**
Nominal Output Voltage
Factory Set Point Tolerance
Output Voltage Adjustment Range
Output Current
Output Power
Line Regulation
Load Regulation
PARD*** (20MHz)
Rise Time
Start-up Time
100Vac
240Vac
Hold-up Time
Dynamic Response (Overshoot & Undershoot O/P Voltage)
Start-up with Capacitive Loads
24Vdc
24Vdc ± 2%
22-28Vdc
0-6.25A (150W max.)
150W
< 0.5% (@ 85-264Vac input, 100% load)
< 0.5% (@ 85-264Vac input, 0-100% load)
< 100mVpp
< 35ms @ nominal input (100% load)
< 1800ms (@ -20°C to 70°C) &
< 2500ms (@ < -20°C to -30°C)
< 1000ms (@ -30°C to 70°C)
> 40ms @ 115Vac, > 50ms 230Vac (100% load)
± 5% @ 85-264Vac input, 0-100% load
(Slew Rate: 0.1A/μS, 50% duty cycle @ 5Hz to 100Hz)
8,000µF Max
(@ > -20°C, 85-264Vac input & @ ≤ -20°C, 100-264Vac input)
**For power de-rating from < -20°C to -30°C, and 50°C to 70°C, see power de-rating on page 3.
. ***PARD is measured with an AC coupling mode, 5cm wires, and in parallel with 0.1µF ceramic capacitor & 47µF electrolytic capacitor
2
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2017, Rev.03)