24V 60W 3 Phase / DRP024V060W3B□
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
Input Voltage Range*
Nominal Input Frequency
Input Frequency Range
DC Input Voltage Range**
Input Current
Efficiency at 100% Load
Max Inrush Current (Cold Start)
Leakage Current
*Fulfills test conditions for up to 600Vac input voltage.
**Fulfills the test conditions for this range.
Output Ratings / Characteristics
Nominal Output Voltage
Output Voltage Tolerance
Output Voltage Adjustment Range
Output Current
Output Power
Line Regulation
Load Regulation
PARD (20MHz)
Rise Time
Start-up Time
Hold-up Time
Dynamic Response (Overshoot & Undershoot O/P Voltage)
Start-up with Capacitive Loads
3 x 400-500Vac
3 x 320-600Vac (3-Phase) or 2 x 360-600Vac (2-Phase)
50-60Hz
47-63Hz
450-800Vdc
< 0.30A @ 3 x 400Vac, < 0.25A @ 3 x 500Vac
> 86.0% @ 3 x 400Vac & 3 x 500Vac
< 30A @ 3 x 400Vac & 3 x 500Vac
< 3.5mA @ 500Vac
24Vdc
± 2% (initial set point tolerance from factory)
24-28Vdc
2.50A (continuously operating at 24V)
3.75A (Power Boost for 5 seconds at 24V, refer to the
details in the Functions section)
60W (continuously operating at 24V)
90W (Power Boost for 5 seconds at 24V, refer to the
details in the Functions section)
< 0.5% typ. (@ 320-600Vac input, 100% load)
< 1% typ. (@ 320-600Vac input, 0-100% load)
< 150mVpp
< 100ms @ nominal input (100% load)
< 1,000ms @ nominal input (100% load)
> 20ms @ 3 x 400Vac,
> 40ms @ 3 x 500Vac (100% load)
± 5% @ 0-100% load
10,000µF Max
2
All parameters are specified at 25°C ambient unless otherwise indicated.
www.DeltaPSU.com (May 2014, Rev. 02)