English
Language : 

NQB-420DWA-AN Datasheet, PDF (17/36 Pages) CUI INC – FULLY REGULATED ADVANCED BUS CONVERTERS
CUI Inc │ SERIES: NQB-D │ DESCRIPTION: FULLY REGULATED ADVANCED BUS CONVERTERS
date 02/20/2013 │ page 17 of 36
Electrical Specification
12.45 V, 39 A / 462 W
TP1, TP3 = -40 to +90ºC, VI = 40 to 60 V, sense pins connected to output pins unless otherwise specified under Conditions.
Typical values given at: TP1, TP3 = +25°C, VI = 53 V, max IO, unless otherwise specified under Conditions.
Additional Cout = 3.9 mF, Configuration File: 19010-CDA 102 0314/017
parameter
conditions/description
min
typ
max
units
input voltage range (VI)
40
turn-off input voltage (VIoff)
decreasing input voltage
36
37
turn-on input voltage (VIon)
increasing input voltage
38
39
internal input capacitance (CI)
18
output power (PO)
0
efficiency (η)
50% of max IO
max IO
50% of max IO, VI = 48 V
max IO, VI = 48 V
96.7
95.7
96.8
95.6
power dissipation (Pd)
max IO
21.0
input idling power (Pli)
IO = 0 A, VI = 53 V
2.8
input standby power (PRC)
VI = 53 V (turned off with RC)
0.4
default switching frequency (fs) 0-100% of max IO
133
140
output voltage initial setting
and accuracy (VOi)
TP1 = 25°C, VI = 53 V, IO = 0 A
12.415
12.45
output adjust range (VO)
see operating information
4.0
output voltage tolerance band
(VO)
0-100% of max IO
11.5
line regulation (VO)
max IO
31
load regulation (VO)
VI = 53 V, 0-100% of max IO
500
600
load transient voltage deviation VI = 53 V, load step 25-75-25% of max IO, di/dt =
(Vtr)
1 A/μs
±0.4
load transient recovery time
(ttr)
VI = 53 V, load step 25-75-25% of max IO, di/dt =
1 A/μs
150
ramp-up time (tr) - (from
10−90% of VOi)
10-100% of max IO, TP1 = 25ºC, VI = 53 V
23
start-up time (ts) - (from VI
connection to 90% of VOi)
10-100% of max IO, TP1 = 25ºC, VI = 53 V
39
VI shut-down fall time (tf) -
max IO
3
(from VI off to 10% of VO)
IO = 0 A, CO = 0 mF
7
RC start-up time (tRC)
max IO
27
RC shut-down fall time (tRC) -
max IO
4.5
(from RC off to 10% of VO)
IO = 0 A, CO = 0 mF
7
output current (IO)
0
current limit threshold (Ilim)
VO = 10.8 V, TP1, TP3 < max TP1, TP3
41
44
short circuit current (Isc)
TP1 = 25ºC, see Note 1
14
recommended capacitive load
(Cout)
TP1 = 25ºC, see Note 2
0.1
3.9
output ripple & noise (VOac)
See ripple & noise section, max IO , see Note 3
50
over voltage protection (OVP) TP1, TP3 = 25°C, VI = 53 V, 10-100% of max IO
15.6
sink current (note 4), see operating information
remote control (RC)
trigger level, decreasing RC-voltage
2.6
trigger level, increasing RC-voltage
2.9
Note
1: OCP in hic-up mode
2: Low ESR-value
3: Cout = 100 µF, external capacitance
4: Sink current drawn by external device connected to the RC pin. Minimum sink current required guaranteeing activated RC function.
60
38
40
462
30.5
147
12.485
13.2
12.7
60
700
39
47
6
110
0.7
V
V
V
μF
W
%
%
%
%
W
W
W
kHz
V
V
V
mV
mV
V
µs
ms
ms
ms
s
ms
ms
s
A
A
A
mF
mVp-p
V
mA
V
V
cui.com