3RHP Datasheet, PDF (2/2 Pages) Crydom Inc., – Hybrid Solid State Contactors
Typical Electrical Connection for 3 Phase Applications 5
(For output voltage options 24, 28, 60)
3 Phase AC
Operating Voltage
~~~ VLL
5L3
3L2
1L1
I L1
AC Input/Control Voltage
(E, F, G input versions)
I L3
6T3
4T2
2T1
I L1
DC Input/Control Voltage
(D5, D12, D24 input versions)
DO NOT apply any AC voltage to contactor coil connections, for DC versions only.
3Ø
Load
Optional Electrical Connections for Single Phase Applications 6
(For output voltage options 12, 24, 28, 60)
AC Input/Control Voltage
(E, F, G input versions)
5L3=NC
~Line
120/240 VAC
3L2
Single Phase
Operating Voltage
1L1
Neutral
6T3=NC
I L1
R1
DC Input/Control Voltage
(D5, D12, D24 input versions)
IL1 ≤ Rated current
3 Phase RHP - Hybrid Solid State Contactors
~Line
120/240 VAC
Single Phase
Operating Voltage
5L3
3L2
1L1
Neutral
Line
5L3
120/240 VAC
Single Phase
Operating Voltage
~
3L2
1L1
7
AC Input/Control Voltage
(E, F, G input versions)
I L3
I L2
R2
R1
I L1
DC Input/Control Voltage
(D5, D12, D24 input versions)
IL1 = (IL2 + IL3) ≤ Rated current
AC Input/Control Voltage
(E, F, G input versions)
I L3
I L2
R2
NC
R1
Neutral
DC Input/Control Voltage
(D5, D12, D24 input versions) IL2 ≤ Rated current
IL3 ≤ Rated current
IL2 + IL3 > Rated current
5 Match VLL to voltage suffixes 28 & 60 for options E, F & G and 12 & 24 for options DX.
6 The single phase supply voltage must be wired to terminal 1L1 and 3L2 for proper single phase operation.
7 In applications switching two single phase loads (R1 and R2) where the combined load current exceeds
the contactor’s rating (40 or 50 Amps) the return/neutral lead must not be wired through the contactor
(see above drawing).