3RHP Datasheet, PDF (1/2 Pages) Crydom Inc., – Hybrid Solid State Contactors
3 Phase RHP - Hybrid Solid State Contactors
3 Phase Contactor
AC Input
40-50 Amp
PPAENTDENINTG
280/600 VAC
Combined SSR and EMR advantages
Lifetime >2 million operations @ full load
No heat sink required
Input status LED indicator
Wire, lug or quick connect termination
DP contactor footprint
CE compliant & UL/cUL recognized
CONTROL SPECIFICATIONS 1
Control Voltage Suffix
Coil Voltage Range
Min. Turn-On Voltage
E
20 - 26 VAC, 50/60 Hz
20 VAC
Min. Turn-Off Voltage
12 VAC
Coil Power Consumption, Inrush 56 VA @ 24 VAC
Coil Power Consumption, Sealed 6.6 VA @ 24 VAC
Coil Terminals
10 in lb (1.13 Nm)
F
100 - 130 VAC, 50/60 Hz
100 VAC
24 VAC
56 VA @ 120 VAC
6.6 VA @ 120 VAC
10 in lb (1.13 Nm)
G
208 - 240 VAC, 50/60 Hz
208 VAC
48 VAC
56 VA @ 220 VAC
6.6 VA @ 220 VAC
10 in lb (1.13 Nm)
OUTPUT SPECIFICATIONS 1
Voltage suffix
Operating Voltage (50/60Hz)
Maximum Off-State Leakage Current per channel 3
28
24 - 280 VAC
0.05 mA @ 240 VAC
60
48 - 600 VAC
0.06 mA @ 480 VAC
Load Current suffix
Maximum Load Current per Phase @ 40°C 2
Power terminals / wire range
Screw torque requirements
40
40 A Resistive
Dual quick connect and Binder
head screws / AWG#14 - AWG#8
18 in lbs (2.1 Nm)
50
50 A Resistive
Dual quick connect and Box
lugs / AWG#14 - AWG#6
25 in lbs (2.9 Nm)
GENERAL SPECIFICATIONS 1
Input to Output Dielectric Isolation.
4000 VAC
Input/Output to Ground Dielectric Isolation.
2500 VAC
Contacts (Double Break ) 3
Three Normally Open
Ambient Operating Temperature Range 4
-20°C to 75°C
Ambient Storage Temperature Range
-40°C to 100°C
Max. Turn-On Time
Max. Turn-Off Time
16.6 mS @ 60 Hz / 20 mS @ 50 Hz
32 mS @ 60 Hz / 40 mS @ 50 Hz
Maximum Number of Operations per Minute
30 operations per min
Lifetime @ Rated Load Current, 40°C ambient
temp, 30 operations/min, Rated Vcontrol
Weight (typical)
> 2 Million operations
540 grs (1.19 lb)
1 Specificationts @ 25°C unless otherwise noted.
2 See Derating Curves for additional operational conditions.
3 The RHP includes a Solid-State Relay. Therefore, the output is never completely open.
4 The RHP includes an overtemperature protection for the Solid-State Module.
3 Phase Contactor
DC Input
40-50 Amp
PPAENTDENINTG
120/240 VAC
Combined SSR and EMR advantages
Lifetime >2 million operations @ full load
No heat sink required
DC logic compatible input
Input status LED indicator
Wire, lug or quick connect termination
DP contactor footprint
CE compliant & UL/cUL recognized
CONTROL SPECIFICATIONS 1
Control Voltage Suffix
D5
D12
D24
Control Voltage Range
4.5 - 5.5 VDC
10 - 15 VDC
22 - 27 VDC
Max. Reverse Voltage
-5.5 VDC
-15.5 VDC
-27.5 VDC
Min. Turn-On Voltage
4.5 VDC
9.5 VDC
9.5 VDC
Min. Turn-Off Voltage
Input Current
1 VDC
12mA @ 5 VDC
2 VDC
12mA @ 12 VDC
2 VDC
12mA @ 24 VDC
Input Connector
5.31 in lb (0.6 Nm) 5.31 in lb (0.6 Nm) 5.31 in lb (0.6 Nm)
OUTPUT SPECIFICATIONS 1
Voltage suffix
12
24
Operating Voltage (50/60Hz)
100 - 120 VAC
Maximum Off-State Leakage Current per channel 3 0.05 mA @ 120 VAC
208 - 240 VAC
0.06 mA @ 240 VAC
Load Current suffix
Maximum Load Current per Phase @ 40°C 2
Power terminals / wire range
Screw torque requirements
40
50
40 A Resistive
50 A Resistive
Dual quick connect and Binder Dual quick connect and Box
head screws / AWG#14 - AWG#8 lugs / AWG#14 - AWG#6
18 in lbs (2.1 Nm)
25 in lbs (2.9 Nm)
GENERAL SPECIFICATIONS 1
Input to Output Dielectric Isolation
Input/Output to Ground Dielectric Isolation
Contacts (Double Break) 3
Ambient Operating Temperature Range 4
Ambient Storage Temperature Range
Max. Turn-On Time
Max. Turn-Off Time
Maximum Number of Operations per Minute
Lifetime @ Rated Load Current, 40°C ambient
temp, 30 operations/min, Rated Vcontrol
Weight (typical)
4000 VAC
2500 VAC
Three Normally Open
-20°C to 75°C
-40°C to 100°C
16.6 mS @ 60 Hz / 20 mS @ 50 Hz
32 mS @ 60 Hz / 40 mS @ 50 Hz
30 operations per min
> 2 Million operations
540 grs (1.19 lb)
1 Specificationts @ 25°C unless otherwise noted.
2 See Derating Curves for additional operational conditions.
3 The RHP includes a Solid-State Relay. Therefore, the output is never completely open.
4 The RHP includes an overtemperature protection for the Solid-State Module.
Part Number Nomenclature
Load Current
40: 40 Amps
SERIES
50: 50 Amps
3 RHP 12 40 D5
Three
Phase
Device
Operating
Voltage VAC
50/60 Hz
12: 120 V 1-phase
24: 240 V 3-phase
or 1-phase
28: 280 V 3-phase
60: 600 V 3-phase
Nominal Coil
/Control Voltage
D5: 5 VDC
D12: 12 VDC
D24: 24 VDC
E: 24 VAC
F: 120 VAC
G: 220 VAC
Derating Curves
3RHPXX40XX
45
40
35
Power lead size
AWG # 6
AWG # 8
30
Safe Operating Area
25
20
25
35
45
55
65
75
Ambient Temperature, °C
3RHPXX50XX
55
50
45
Power lead size
40
AWG # 6
AWG # 8
35
30
Safe Operating Area
25
20
25
35
45
55
65
75
Ambient Temperature, °C