English
Language : 

D53TP50D-10 Datasheet, PDF (1/6 Pages) Crydom Inc., – 53TP Series IP00
DataSPahneel Meoutnt
53TP Series IP00
• Three-phase solid-state relay; Ratings 25 A, 50 A per phase @ 48-530 VAC
• 2 package styles IP00 or IP20 (See IP20 spec sheet for more information)
• SCR output for heavy industrial loads
• Transient protection built in
• AC or DC control
• Zero-crossing (resistive loads) or random-fire (inductive loads) output
• LED input status indicator
• UL Recognized, CE Compliant to EN60950-1
PRODUCT SELECTION
Control Voltage
90-280 VAC
4-32 VDC
25 A
A53TP25D
D53TP25D
50 A
A53TP50D
D53TP50D
AVAILABLE OPTIONS
Series
A 53TP
Control Voltage
D: DC (4-32V)
A: AC (90-280V)
Load Current
25: 25 Amps
50: 50 Amps
25 D
Required for valid part number
For options only and not required for valid part number
Switching Mode
Blank: Zero Voltage Turn-On
-10: Random Turn-On
H -10
Thermal Pad
Blank: Not Included
H: Included
OUTPUT SPECIFICATIONS AC Output (1)
Description
Operating Voltage (47-63Hz) [Vrms]
Transient Overvoltage [Vpk] (2)
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/μsec] (3)
Maximum Load Current [Arms] (4)
Minimum Load Current [Arms]
Maximum Surge Current 50-60 Hz (16.6ms) [Apk]
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Thermal Resistance Junction to Case (Rjc) [°C/W]
Maximum I²t for Fusing 50-60 Hz (8.3 msec) [A² sec]
Minimum Power Factor (with Maximum Load)
25 A
48-530
1200
10
500
25
0.05
239/250
1.6
1.02
285/260
0.5
50 A
48-530
1200
10
500
50
0.05
597/625
1.6
0.63
1779/1620
0.5
Do not forget to visit us at: www.crydom.com