English
Language : 

SM363FG Datasheet, PDF (4/32 Pages) Cooper Bussmann, Inc. – Safety Module fused disconnect switch
Disconnects
Coordination Module™ fused lighting and
appliance panelboard
Type EP
Cooper Bussmann® Coordination Module™
Specifications
Description: A fused lighting and appliance panelboard for
branch circuit applications. Specifically designed to meet the
2005 NEC® Code requirements for selective coordination for
Emergency, Legally Required Standby and Essential Electrical
Systems per 700.27, 701.18, and 517.26 when properly coordi-
nated with the upstream overcurrent protective device feeder.
Circuits: 12, 24, 36, 42
Enclosure: NEMA 1
Ratings:
Volts: — 120/208 or 277/480Vac
Branch Circuit Amps: — 0-30A
SCCR: — 100kA
Agency Information: UL67, UL 50.
Features and Benefits
• Complies with the new 2005 NEC® Selective Coordination
Requirements for Emergency, Legally Required Standby and
Essential Electrical Systems per 700.27, 701.18, and 517.26
when properly coordinated with the upstream overcurrent
protective device feeder. Per the 2005 NEC®: Coordination
(Selective) is the localization of an overcurrent condition to
restrict outages to the circuit or equipment affected,
accomplished by the choice of overcurrent protective devices
and their ratings or settings.
• Ensures system uptime with the goal of safety of human life
during emergencies or for essential health care functions.
• Provides a fast and easy solution to meeting new coordination
Code requirements. Simply utilize published fuse selective
coordination ratios to select the correct upstream fuse ratings.
• Offers significant savings compared to other fused panels and
selectively coordinated circuit breaker systems.
Typical Applications
• Hospitals
• Schools
• Commercial and industrial facilities
Catalog Numbers Coordination Module*
Voltage
Catalog Numbers Rating
SCCR
EP2M23012GCC 120/208
100kA**
EP2M23024GCC 120/208
100kA**
EP2M23036GCC 120/208
100kA**
EP2M23042GCC 120/208
100kA**
EP4M23012GCC 277/480
100kA***
EP4M23024GCC 277/480
100kA***
EP4M23036GCC 277/480
100kA***
EP4M23042GCC 277/480
100kA***
Dimensions (in)
Height Width Depth
36
28
5 3⁄4
38
28
5 3⁄4
48
28
5 3⁄4
48
28
5 3⁄4
36
28
5 3⁄4
36
28
5 3⁄4
48
28
5 3⁄4
48
28
5 3⁄4
* Meets UL 67 (Panelboards) and UL 50 (Cabinets and Boxes).
** When protected by upstream LPN-RK 100A max. LPJ 200A max. or JJN 200A max., otherwise 10kA.
*** When protected by upstream LPN-RK 200A max. LPJ 200A max. or JJN 200A max., otherwise 14kA.
Type
MLO
MLO
MLO
MLO
MLO
MLO
MLO
MLO
Main Device
Amp Rating
200
200
200
200
200
200
200
200
Branch Circuit
Amp Number of
Rating Circuits
30
12
30
24
30
36
30
42
30
12
30
24
30
36
30
42
310