English
Language : 

SM363FG Datasheet, PDF (30/32 Pages) Cooper Bussmann, Inc. – Safety Module fused disconnect switch
Disconnects
A/C Disconnects — fused and non-fused
Series B22__
Specifications
Description: Fused and non-fused rainproof air conditioner
pullout units.
Dimensions: See Catalog Numbers table.
Construction: NEMA 3R rainproof metal housing with
weather resistant coating.
Wire Range: 14-3 AWG, AL/CU
Ratings:
Phase: — Single, 2-wire
Volts: — 240Vac
Amps: — 30-60A
Agency Information: UL Listed to UL 1429, C-UL
Certified, UL Guide WGEW
Features and Benefits
• A/C disconnects meet NEC® Code Requirements under
articles 440.14. GFCI units meet NEC® Code Requirements
under articles 210.63, 210.8, and 406.8(B)(1).
• NEMA 3R rainproof enclosures withstand outdoor
environment.
• Padlockable with two-position pullout handle to lock safety
shield when in the ON position. (Not available on GF or NA
units.) For added safety, pullout handle can be stored in the
compartment in the off position.
• Easy installation: knockouts on back, bottom and both sides,
Cable whip versions save labor.
Metallic Fused Disconnect
Metallic Non-Fused Disconnect
Metallic Non-Fused
Disconnect with GFCI
receptacle.
Typical Applications
• Residential, light industrial/commercial A/C and heat pump
service.
• Spas/whirlpools, swimming pools, pump houses
• Suitable for service entrance equipment applications with
field installable ground bar, kit number DPFG.
B222-60NF34W non-fused with cable whip
Catalog Numbers
Fused
Catalog Numbers
B221-30F
B221-30FGF
B222-60F
B222-60FGF
Description
30A, Pullout
30A, Pullout w/ GFCI
60A, Pullout
60A, Pullout w/ GFCI
Disconnect
Rating
30A
30A
60A
60A
Non-Fused
B222-60NF
60A, Pullout
60A
B222-60NFGF
60A, Pullout w/ GFCI
60A
B222-60NFNA
60A, Switch
60A
Non-Fused Cable Whip
B222-60NF12W
B222-60NF34W
60A, Pullout w/ 1⁄2" Cable Whip
60A, Pullout w/ 3⁄4" Cable Whip
60A*
60A**
Max Hp Rating
120V
240V
1.5
3
1.5
3
3
10
3
10
3
10
3
10
*
10
3
10
3
10
Wire Range
60 or 75°C CU/AL
#14-3
#14-3
#14-3
#14-3
Enclosure
Type
NEMA 3R
NEMA 3R
NEMA 3R
NEMA 3R
#14-3
#14-3
#14-3
NEMA 3R
NEMA 3R
NEMA 3R
#14-3
#14-3
NEMA 3R
NEMA 3R
Fuse
Class
H or R
H or R
H or R
H or R
Approx. Dimensions (in)
Height Width Depth
8 3⁄4
5 3⁄8
2 7⁄8
13
7 1⁄2
4 3⁄4
8 3⁄4
5 3⁄8
2 7⁄8
13
7 1⁄2
4 3⁄4
*
8 3⁄4
5 3⁄8
2 7⁄8
*
11 3⁄4
6 1⁄2
4 1⁄2
*
8 3⁄4
5 3⁄8
3 5⁄8
*
14 3⁄4
12 1⁄2 4
*
14 3⁄4
12 1⁄2 4
Cable Whip Specifications
Pullout
Catalog Numbers Description
Rating
B222-60NF12W 60A, Pullout w/ 1⁄2" Cable Whip
60A
B222-60NF34W 60A, Pullout w/ 3⁄4" Cable Whip
60A
* Upstream overcurrent protection device (OCPD) not to exceed 30 Amps.
**Upstream overcurrent protection device (OCPD) not to exceed 50 Amps.
Max UpstreamWire
Overcurrent Harness
Protection Device Diameter
30A
1⁄2"
50A
3⁄4"
Ground Hot Flexible
Wire Size Wire Size
#10
#10
#8
#10
Conduit
Length (ft)
6
6
Non-Metallic Fittings
1 - 90°, 1 - Straight
1 - 90°, 1 - Straight
Data Sheet: 1143
336
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp