English
Language : 

FWP-30A14FI Datasheet, PDF (4/21 Pages) Cooper Bussmann, Inc. – Ferrule fuses
High Speed Fuses
Ferrule — FWX 250V (UL): 1-50A
FWX (14 x 51mm)
Specifications
Description: Ferrule style high
speed fuses.
Dimensions: See dimensions
illustration.
Ratings:
Volts: — 250Vac/dc
Amps: — 1-50A
IR: — 200kA RMS Sym.
— 50kA @ 250Vdc
Agency Information: CE, UL Recognition 1-50A & CSA
Component Acceptance: 5-30A
Electrical
Characteristics
Total Clearing I2t
The total clearing I2t at
rated voltage and at power
factor of 15% are given in
the electrical
characteristics. For other
voltages, the clearing I2t is
found by multiplying by
correction factor, K, given
as a function of applied
working voltage, Eg, (rms).
1.5
K
1.0
0.5 1)
2)
0.3
0.2
0.15
75 125
200 250
Eg
300
Dimensions - mm (inches)
50.8
(2.000")
14.3
(0.563")
15.5
(0.610")
Arc Voltage
This curve gives the
peak arc voltage, UL,
which may appear
1.4
1.2 UL
103
800
across the fuse during 600
its operation as a
500
function of the applied
working voltage, Eg,
(rms) at a power factor
400 1)
300
2)
of 15%.
Power Losses
200
50 100 150
Watts loss at rated current
1.0
0.8
Kp
is given in the electrical 0.6
characteristics. The curve 0.5
allows the calculation of 0.4
the power losses at load 0.3
currents lower than the
rated current. The
0.2
correction factor, Kp, is
given as a function of the
RMS load current, Ib, in %
0.1
30
40
50
60
70
of the rated current.
Eg
200 250
Ib
80 90 100%
Catalog Numbers
Electrical Characteristics
Rated
I2t (A2Sec)
Catalog
Current
Clearing Watts
Number
Size
RMS-Amps Pre-arc
at 250V Loss
FWX-1A14F
1
—
—
—
FWX-2A14F
2
—
—
—
FWX-3A14F
3
—
—
—
FWX-4A14F
4
—
—
—
FWX-5A14F 14 x 51mm
5
1.6
13
1.3
FWX-10A14F (9⁄16” x 2”)
10
FWX-15A14F
15
3.6
24
3.4
14
83
3.8
FWX-20A14F
20
33
200
4.6
FWX-25A14F
25
58
300
5.3
FWX-30A14F
30
100
500
5.9
FWX-50A14F
50
200
1800
5.7
• Watts loss provided at rated current.
• (250Vdc/Interrupting rating 50kA) UL Recognition & CSA Component Acceptance on 5
through 30A only. Consult Cooper Bussmann for additional ratings.
• See accessories on page 216.
Features and Benefits
• Excellent cycling capability and DC performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss in a compact size
• Used with finger-safe holders/blocks
Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters
Data Sheet: 720006
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
199