FWP-30A14FI Datasheet, PDF (20/21 Pages) Cooper Bussmann, Inc. – Ferrule fuses | |||
|
◁ |
High Speed Fuses
Ferrule â FWS/FWL 1000Vdc: 2-30A
FWS 2-15A (20 x 127mm)
FWL 20-30A (20 x 127mm)
Specifications
Description: Ferrule style full range
fuses.
Dimensions: See dimensions
illustrations.
Ratings:
Volts: â 1200Vac (FWL 20-30A)
â 1400Vac (FWS 8-15A)
â 2100Vac (FWS 2-6A)
â 1000Vdc (FWL/FWS 2-30)
Amps: â 2-30A
IR: â 45kA RMS Sym.
â 30kA @ 1000Vdc
Agency Information: CE, IEC 60077
Catalog Numbers
Electrical Characteristics
Rated
I2t (A2 Sec)
Catalog
Current
Clearing
Numbers
Size
RMS-Amps Pre-arc at 1000Vdc
FWS-2A20F
2
0.8
2.4
FWS-6A20F
6
27
81
FWS-8A20F 20 x 127mm
8
64
192
FWS-10A20F (13â16â x 5â)
10
FWS-12A20F
12
118
277
170
380
FWS-15A20F
15
209
500
FWL-20A20F
FWL-25A20F
FWL-30A20F
20 x 127mm
(13â16â x 5â)
20
25
30
675
1200
1850
1550
2760
4300
⢠ADD âIâ to catalog number for indicating version.
⢠Enclosed finger-safe fuse holder â CH127
⢠Open style fuse block â 4530-OP
⢠See accessories on page 216.
⢠Watts loss provided at rated current.
Watts
Loss
4.4
6.7
7.6
3.0
3.4
5.0
5.9
6.5
7.5
Dimensions - mm (inches)
127.0
(5.000")
20.5
(0.807")
Features and Benefits
⢠Excellent cycling capability and DC performance
⢠Low arc voltage and low energy let-through (I2t)
⢠Low watts loss in a compact size
⢠Used with finger-safe holders/blocks
Typical Applications
⢠DC common bus
⢠DC drives
⢠Power converters/rectifiers
⢠Reduced voltage starters
⢠Traction aux circuits
⢠Capacitor protection
FWL/FWS 2-30A: 1000Vdc 2-30A
(20 x 127mm)
Time-Current Curve
16.0
(0.630")
Indicating Version â Dimensions - mm (inches)
8.0
(0.315")
127.0
(5.000")
20.5
(0.807")
2.0
Data Sheet: 720040
16.0
(0.630")
2.0
(0.079")
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa