English
Language : 

DS1050-3 Datasheet, PDF (2/4 Pages) Artesyn Technologies – Distributed Power Bulk Front-End
DS1050 Data Sheet
Logic Control
PS_SEATED (A4)
PWR GOOD (C3)
AC OK (B1)
PS_INHIBIT/PS_KILL (B4)
PS ON (A1)
TTL logic LOW if power supply is seated into system connector. This is a short pin. A logic HIGH if the PSU is removed
Active TTL high when output is within regulation limits.
A low logic level if the input voltage is within allowable limits. A TTL logic HIGH level, and a 5mS early warning signal
before 12.0 V DC output loss of regulation.
This signal is connected to a short pin on the PSU
When left open power supply operation will be inhibited. When the power supply is inserted into the system, this pin
will be pull low by the system and turn the power supply on only after all other power supply pins have seated.
The output will be enabled when this signal is pulled low, below 0.8 V outputs disabled when pin is driven high or left
open.
Environmental Specifications
Operating temperature
Storage temperature
Altitude, operating
Electromagnetic susceptibility/Input transients
RoHS & lead-free compliant
Humidity
Shock and vibration specificatons
MTBF (Demonstrated)
-10 °C to 50 °C ; 50% power derating at 70 °C
-40 °C to +85 °C
10,000 ft
-EN61000-3-2, -3-3
-EN61000-4-2, 4.3, 4-4, -4-5, 4-11
-EN55024:1998
No tantalum caps.
20 to 90% RH, non-condensing
Standard operating/non-operating random shock/vibration
500K Hrs at full load, 40 °C
Ordering Information
Model Number
Nominal Output
Voltage Set Point
Set Point
Tolerance
Total Minimum Maximum Output Ripple
Regulation Current Current
P/P
Over Current
Standby** Air Flow
DS1050-3
12.0 Vdc
±0.2%
±5%
0A
87 A
120 mV 102.7 A - 128.4 A 3.3 V @ 4 A STD
DS1050-3-001
12.0 Vdc
±0.2%
±5%
0A
87 A
120 mV 102.7 A - 128.4 A 3.3 V @ 4 A REV
DS1050-3-002
12.0 Vdc
±0.2%
±5%
0A
87 A
120 mV 102.7 A - 128.4 A 5.0 V @ 2.5 A STD
DS1050-3-003
12.0 Vdc
±0.2%
±5%
0A
87 A
120 mV 102.7 A - 128.4 A 5.0 V @ 2.5 A REV
*Overcurrent latches off if overcurrent lasts over 1 seconds, otherwise it is auto recovery.
** 3.3 V standby can operate at 6 A, but overall unit efficiency will fall slightly below Gold Standard.